2. Modbus
2.1.
Configuration of parameters
•
Communication speed:
between 2400 and 115200 bauds, 19200 bauds by default
•
Data bits:
8 bits
•
Stop bit:
1 bit
•
Parity:
None
•
Flow control:
None
•
Transmitter addressing:
between 1 and 255
(automatically answers the requests from address 0)
•
Data sending:
made by words of 2 bytes, in the following order: most-significant then least-significant byte
2.2.
Functions
•
Register function:
Function 03
•
Register writing:
Function 16
•
Communication loop test:
Function 08
2.3.
Access code to register
•
Registers type:
Type
Size
Description
Format
U8
1 byte
Unsigned integer 8 bits Byte 1
Example with a value of
24 (0x18)
0x18
Type
Size
Description
Format
U16
2 bytes
Unsigned integer 16
bits
Byte 2
Byte 1
Example with a value of
300 (0x
01
2C
)
0x01
0x2C
Type
Size
Description
Format
U32
4 bytes
Unsigned integer 32
bits
Byte 2
Byte 1
Byte 4
Byte 3
Example with a value of
1 096 861 217
(0x
41
60
C6
21
)
0xC6
0x21
0x41
0x60
Type
Size
Description
Format
Real
4 bytes
Real 32 bits
Byte 2
Byte 1
Byte 4
Byte 3
Example with a value of
153.5 (0x
43
19
80
00
)
0x80
0x00
0x43
0x19
Type
Size
Description
Format
Enumeration
1 byte
See Enumeration table
page 8
Same as U8
Boolean
1 byte
True = 1 ; False = 0
Same as U8
6
Modbus