6.3.2
Perform the output diagnostic
Once the connection to the measurement device is performed, you can carry out the analogue output diagnostics on
several check points.
The transmitter is powered on.
➢
Press OK.
➢
Enter the activation code (see page 9).
➢
Press OK.
➢
Press Up key to go to
F303
folder.
➢
Press OK.
F 303 blinks, corresponding to the folder of the
channel 1
diagnostic
.
➢
Press OK.
➢
Press Up and Down keys to select the signal the transmitter must generate.
Display
Generated output
Example
1/3
Simulates 0% of the output range
On the range 0-10V, the transmitter will generate 0 V.
2/3
Simulates 50% of the output range
On the range 0-10V, the transmitter will generate 5 V.
3/3
Simulates 100% of the output range
On the range 0-10V, the transmitter will generate 10 V.
If the deviations are too large (>0,05V or >0,05mA) between the signal issued and the value displayed on
the multimeter, we recommend that you return the transmitter to our factory.
For the diagnostic of the
channel 2
, go to
F 313
folder and perform the same procedure as for the channel 1.
For the diagnostic of the
channel 3
, go to
F 323
folder and perform the same procedure as for the channel 1.
Measurement conversion charts:
•
Pressure
Pa
mmH
2
O
InWG
mbar
mmHG
kPa
daPa
hPa
±100
±10.2
±0.40
±1.00
±0.75
±0.100
±10.0
±1.00
±1000
±102.0
±4.01
±10.00
±7.50
±1.000
±100.0
±10.00
•
Temperature
°C
°F
From 0.0 to +50.0
From +32.0 to +122.0
From -20.0 to +80.0
From -4.0 to +176.0
From -40.0 to +180.0
From -40.0 to +356.0
From -100.0 to +400.0
From -148.0 to +752.0
16
F 300: Manage the analogue outputs