Chapter 3: Configuration and commissioning
KFP-CX3E Series Installation Manual
61
Display
Description
Value
Module A output 2 delay
00 to 10 minutes
Module A output 3 delay
00 to 10 minutes
Module A output 4 delay
00 to 10 minutes
Expansion board function
Use this menu to configure the expansion board function. The default value is 41.
For available presets, see “Expansion board functions” on page 91.
To configure the expansion board function:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED on the control panel interface and the
ON LED on the expansion board flashes fast to indicate that the module
function configuration menu is active.
2. Select a value from 01 to 96 using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
Expansion board output delay
Use this menu to configure an expansion board output delay of up to 10 minutes,
where the feature is available.
To configure an expansion board output delay:
1. For output 1 on expansion board A, set the display as shown below, and then
press Enter.
The Expansion I/O Fault/Disabled LED on the panel and the output 1
Activated LED on the expansion board flash fast to indicate that the delay
menu is active.
2. Select a value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
Содержание KFP-CX3E Series
Страница 1: ...KFP CX3E Series Installation Manual P N 501 419403 1 10 REV 01 ISS 12MAR14 ...
Страница 6: ...iv KFP CX3E Series Installation Manual ...
Страница 28: ...Chapter 2 Installation 22 KFP CX3E Series Installation Manual ...
Страница 80: ...Chapter 3 Configuration and commissioning 74 KFP CX3E Series Installation Manual ...
Страница 84: ...Chapter 4 Maintenance 78 KFP CX3E Series Installation Manual ...
Страница 104: ...Appendix A Configuration presets 98 KFP CX3E Series Installation Manual ...
Страница 108: ...Appendix B Regulatory information 102 KFP CX3E Series Installation Manual ...
Страница 111: ......
Страница 112: ......