Chapter 3: Configuration and commissioning
KFP-CX3E Series Installation Manual
55
The available settings for this feature are shown below.
Display
Description
The fault latch is enabled.
The fault latch is disabled.
Zone configuration
Use this menu to configure zone settings for each zone in your fire alarm system.
To configure the zone:
1. Set the display as shown below, and then press Enter.
2. Select the zone (for example, zone 1), and then press Enter.
The red Zone LED flashes fast to indicate that the corresponding zone
configuration menu is active.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
5. Save your changes.
The available settings for this feature are shown below.
Display
Description
Passive end-of-line
Active end-of-line
Passive end-of-line with CleanMe
Active end-of-line with CleanMe
Intrinsically safe