Chapter 3: Configuration and commissioning
30
KFP-CX3E Series Installation Manual
The control panel will exit configuration mode after 5 minutes if no button is
pressed.
Visible indications for current value and selected value
Current and selected values are indicated as follows.
Table 12: Visible indications for values
Status
Indication
Current value
Both decimal points on the display
are steady
New selected value Both decimal points on the display
are flashing
Other value
Both decimal points on the display
are off
To restore the previous configuration:
1. Set the display as shown below, and then press Enter.
To restore the factory configuration:
1. Set the display as shown below, and then press Enter.