Connection
The module connectors, DIP switch, and status LED are
shown in Figure 1:
1. Earth screw
2. Loop connectors
3. Auxiliary power supply connectors
4. Relay output connectors (C, NC, NO)
5. DIP switch
6. Status LED
Loop overloading
Always verify large installations using a loop load calculator to
confirm that enough power is available on the loop.
Note:
To avoid loop overloading when using loop-powered
devices, see the system installation and configuration
guidelines in the Loop Power and I/O Modules Application
Note. This document is available from your local distributor.
Power supply configuration
To set the module power supply, remove the unit cover and
configure jumpers JMP1 and JMP2.
Loop powered jumper
configuration.
24 VDC auxiliary power supply
jumper configuration.
WARNING:
Do not connect a 24 VDC auxiliary power supply
to the module if power is supplied by the loop
Addressing
Each module requires a numeric address between 128 and
252 for identification purposes. This is set using DIP switches
1-7. See the address table at the end of this document.
Status LED
The status-LED (Figure 1, item 6) is configured using DIP
switch 8:
•
If set to ON the LED will flash during all communications
between the module and the control panel.
•
If set to OFF it will flash only during selected
communications between the module and control panel
(see control panel manual for further details).
The status LED is lit constantly during alarm.
Maintenance and testing
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry. To test the module:
1. Configure the module as an output to be activated by a
detector or manual call point.
2. Remove a detector head from its base or activate a
manual call point.
3. If the status-LED and control panel fail to indicate the test
all connections should be checked and the module
address verified.
Specifications
Operating voltage
22 to 38 VDC
Relay contact rating
Max.switching voltage
Nominal current
AC: 42 V peak / DC: 30 V
AC: 0.5 A / DC: 0.5 A
Operating temperature
Storage temperature
−10 to +50ºC
−10 to +70ºC
Relative humidity
10 to 95% (non condensing)
Weight
370 g
Dimensions
182 × 142 × 77 mm
Current consumption (externally powered)
Loop current consumption
at 24 VDC (standby)
at 35 VDC (standby)
Alarm
70 µA
100 µA
<3.5 mA
Current consumption
24 VDC aux. supply
(standby)
24 VDC aux. supply (alarm)
22 mA
<50 mA
Current consumption (loop powered)
Loop current consumption
Standby
Alarm
350 µA
<3.4 mA
Certification and compliance
Description
Addressable Relay Output Module
Certification
CPD certificate
1438-CPD-0138
Year of manufacture
The year of manufacture is included in
the first two digits of your product serial
number (located on the product
identification label).
EN54
EN54-18
EMC
EN 50130-4
EN 61000-6-3
Manufacturer
UTC Fire & Security, 129 North Main
Street, Pittsfield, Maine 04967, USA.
Manufacturer’s
representative (Europe)
UTC Fire & Security B.V. Kelvinstraat 7,
6003 DH Weert, Netherlands.
ES: Instrucciónes de instalación
Descripción
El módulo KAL730 proporciona una salida de relé libre de
potencial para un bucle del sistema de detección de incendios
direccionable.
El relé permite la instalación de contactos comunes (C),
normalmente cerrados (NC) y normalmente abiertos (NA). El
módulo puede utilizarse con cualquier dispositivo y la opción
de contacto utilizada (C, NC o NA) establecerá el evento
deseado.
El módulo es ideal para su uso con una fuente o equipo de
alimentación que requiera una placa de suministro
independiente del sistema de incendios o de parte de otro
sistema. Las salidas de la fuente de alimentación del relé de
24 V están aisladas del resto de la placa.