39 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Device
Setting
Under 40A
Charger
40-60A
Charger
60-150A
Charger
LBCO Hysteresis
2 V
Max Bulk Current
Set to whatever percentage of the inverter
current plus the charge controller current is
less than or equal to 100 A
Absolute
Maximum
Charge Rate
120A per KiloVault® HAB™ V4 in Parallel (Solar
Charge Controller Amps + Percentage of
Inverter/Charger Max DC Output.
Example: For a single KiloVault® HAB™ V4
system with an inverter/charger maximum DC
output of
100 A and a solar charge controller capable of
80 A, you would limit the inverter/charger
output to 40 A (so the total is 120 A).
Recharge / Re-
Bulk Volts (80%
DoD)
51.4 V (used to set voltage that triggers
charge start)
Charge
Controller
Absorb Time
Under 6 min
Under 4 min
Under 2 min
Absorb Voltage
56 V
Battery Capacity
150 Ah (7.5 kWh) per KiloVault® HAB™ V4
Battery
Temperature
Compensation
Do not use an external battery temperature
sensor with these batteries. If the sensor is
required for a charge controller or inverter
charger to work, set the battery temperature
compensation to 0mV / °C.
Battery Type
Lithium Ion or Custom - whichever provides
access to all the required settings
Battery Voltage
48 V
Bulk Voltage
56 V
Charge Cycle
3 Stage
Equalization
Disabled
Max Float
Current
10 A
Float Voltage
54 V