13 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Item
Specification
Recommended Floating Charge
Voltage
52.8 V
Self-Discharge Rate
≤3% per month, ≤15% per year
•
Note: This rate is only achieved
when the KiloVault® HAB™ V4 is
put to sleep by pressing down the
Power button for 10 seconds.
•
If the KiloVault® HAB™ V4 is shut
down using the standard, short, 3-
second-long, power button push,
self-discharge can be as high as 9%
per month.
Refer to Section 6 Troubleshooting for a complete list of protection limits.
3.2.
Operating Environment Specifications
Item
Specification
Operating Environment
Indoors away from direct exposure to
rain or sun
Operating Temperature
32° to 113°F (0° to 45°C)
Recommended Operating
Temperature
59 to 95°F (15°C to 35°C)
Short Term (less than one month)
Storage Temperature
-4 to 110°F (-20° to 45°C)
Absolute Maximum Altitude
13,123 feet (4000 m)
•
To operate the HAB™at 3000m, limit
the output power to max. 6.48Kw
(max 120A)” to “Between 6561 feet
(2000 m) & 9843 feet 3000 m limit,
the output power to 6.48 kW. Do not
operate above 4000 m