12 of 56
Revision 4
KiloVault
®
LLC • 330 Codman Hill Road, Boxborough, MA 01719 • +1 (888) 218-5924 •
• www.kilovault.com
Item
Specification
Full Charge Voltage
56 V
KiloVault® HAB™ V4 to KiloVault®
HAB™ V4 (inter-battery)
communication cable
RJ45 120 Ω Resistor Plug, 6-position, 4-
conductor, male connectors both ends.
Straight through. Maximum length, 10
feet
KiloVault® HAB™ V4 to KiloVault®
HAB™ V4 (inter-battery)
communication protocol
CAN Bus
KiloVault® HAB™ V4 to Inverter
communication protocol
Modbus
High Voltage Cutout
60.0 ± .5 V (not a set point)
Low Voltage Cutout
48.0 V (not a set point)
Maximum Cell Balancing Voltage
70 mA
Maximum Continuous Charge
Current
120 A (not a set point)
Maximum Continuous Discharge
Current
150 A (not a set point)
Maximum Continuous Discharge
Power
7.5 kW
Maximum KiloVault® HAB™ V4 to
KiloVault® HAB™ V4 Cable
Length
9.84 ft (3 m)
Minimum Cell Balancing Voltage
3350 mW
Minimum Discharge Voltage
48.0 V
Nominal Capacity
150 Ah
Nominal Energy
7.68 kWh
Nominal Voltage
51.2 VDC
Operational Temperature Range
32° to 113°F (0° to 45°C)
Peak Discharge Current (3s)
500 A
Peak Discharge Power (3s)
25k W