PWR Series Setup Guide

The power cord that is included with the 1600 W type can be used 
on either a 100-Vac or 200-Vac system.

WARNING

• Possible electric shock. Turn off the circuit breaker of 

switchboard before connecting the cord.

• Possible Fire. Have a qualified engineer connect the 

power cord to the switchboard. The breaker of switch-

board is required to meet requirement.

CAUTION

Inside the product, protective circuits including input fuses 

are connected to match the polarity of the input terminal. 

Make sure the colors of the wires connected to the corre-
sponding input terminals (L, N, and   (GND)) are correct.

- Note -
Turn off the circuit breaker of switchboard to disconnect the PWR 

from the AC line in an emergency.

Circuit breaker of switchboard requirement

•  Rated current: 30 A (100 V system) / 15 A (200 V system) 

For safety, breakers whose rated current exceeds the specified 
current cannot be used

•  Dedicate the circuit breaker for the PWR.
•  Keep the switchboard easily accessible at any time.
•  Require labeling to identify that the circuit breaker is dedicated 

for the PWR and disconnecting device.

PWR1600L

N

L

N

L

Switchboard

Supplied power cord

Breaker dedicated

to the PWR1600L

PWR1600L

30 A

Breaker indication example

Connection to the switchboard (PWR1600L example)

Connecting the Power Cord (Cont.)

1600 W type

Содержание PWR1600H

Страница 1: ...al remote control function through TP BUS Twist Pair BUS communication The total length of TP BUS is 200 m By combining with Kikusui s PIA4800 Series Power Sup ply Controller systemization for applica...

Страница 2: ...GB1002 Rating 250Vac 10A 85 10 0790 or or 1 pc M3 112 012 1 pc M3 112 015 CD ROM 1 pc Setup Guide This guide 1 pc Quick Reference English 1 pc Japanese 1 pc Safety information 1 pc Power cord for the...

Страница 3: ...lost or soiled a new copy can be provided for a fee To replace or purchase a manual please contact your Kikusui agent or distributor At that time inform your agent or distributor of the Part No writt...

Страница 4: ...igured in a way that satisfies the equation output voltage x output current rated output voltage the actual output is limited by the power limit approx 105 of the rated output power and the output vol...

Страница 5: ...Rated output current Extended operating area Intermittent extended operating area Maximum output current Continuous extended operating area Extended operating area Continuous output is possible At amb...

Страница 6: ...d the product to prevent electric shock Connect the ground terminal to earth ground Connecting the Power Cord Precautions Concerning Installation This product cannot be used while it is on its side Th...

Страница 7: ...difficult consult your Kikusui agent or distributor The power cord with a three prong plug is used to disconnect the PWR from the AC line in an emergency Connect the power plug to an easily accessibl...

Страница 8: ...e corre sponding input terminals L N and GND are correct Note Turn off the circuit breaker of switchboard to disconnect the PWR from the AC line in an emergency Circuit breaker of switchboard requirem...

Страница 9: ...es with the input rating of the PWR The voltage that can be applied is any of the nominal power supply voltages in the range of 100 VAC to 240 VAC The frequency is 50 Hz or 60 Hz 2 Check that the POWE...

Страница 10: ...switch is turned off 2 Check that the power cord is correctly connected 3 Turn the POWER switch on Push the side of the POWER switch to turn the PWR on If an odd sound odd odor fire or smoke occurs a...

Страница 11: ...ff The PWR stores the panel settings excluding output on off condi tion immediately before the POWER switch is turned off For these items the PWR starts up using the settings that existed when the POW...

Страница 12: ...e Ammeter reading average value Preset constant current value Ammeter reading average value Load that generates reverse current to the power supply The PWR cannot absorb reverse current from the load...

Страница 13: ...PWR and the load in series CAUTION To protect the load and the PWR select a DRP that com plies with the following conditions Reverse voltage withstand capacity of at least twice the rated output volta...

Страница 14: ...mbient temperature and thermal resistance to the outside Table shows the allowable capacity of current that can flow through a heat resistant PVC wire single wire having a maximum allowable temperatur...

Страница 15: ...voltage drop exceeds this level wires having a greater sectional area should be used Nominal cross sectional area of wires and allowable currents Nominal Cross Sectional Area mm2 AWG Reference Cross S...

Страница 16: ...of AWG18 or higher to make the connection This M3 screw is fastened to the pos terminal before factory shipment If you want to connect the chassis connection wire to the neg output terminal as shown...

Страница 17: ...out screws 2 Align the hook of the bottom cover to the groove lo cated to the side of the output terminal 3 Align the bottom cover with the top cover and fix them in place using the screws attached to...

Страница 18: ...utput terminal on the front panel Do not use the terminal with the front output terminal cover removed In addition be sure to attach the OUT PUT terminal cover on the rear panel Possible overheating o...

Страница 19: ...indows and Visual Basic are registered trademarks of Microsoft Corporation in the United States and or other countries All company names and product names used in the PWR manual are trademarks or regi...

Страница 20: ...i Name of hazardous materials and symbol of element in the equipment and quantity Name of part Hazardous material and symbol of element Pb Hg Cd Cr VI PBB PBDE Printed circuit board assemblies Interna...

Отзывы: