4 PD05M-PCR-LE/PD05S-PCR-LE

Turning the Power On

 

„

Power ON

Turn on the POWER switches on the master unit and all slave units 
within 10 seconds. Alternatively, turn the POWER switches of all 
PCR-LEs ON simultaneously.
The firmware version is displayed for a few seconds.
If there are no errors, the master unit displays the home position (the 
basic screen), and the slave units display "SLAVE-x" (where x is the 
slave unit number).
Master-slave parallel operation is controlled from the master unit. 
You cannot use the panel of the slave unit.

 

„

Power OFF

Turn off all POWER switches.
For emergency situations, we recommend that you insert a circuit 
breaker that separates the entire system from the switchboard.

Synchronizing the POWER Switches

You can configure the system so that when you turn on MASTER 
unit, all SLAVE units also turn on.

 

„

Power ON

 

Check that the POWER switches of PCR-LEs series 

are off.

 

Set the POWER SELECTOR switch of the PCR-LE  

master unit to MASTER.

The POWER SELECTOR switch is on the front panel.

 

Set the POWER SELECTOR switches of the other 

PCR-LEs to SLAVE.

  

Turn ON the POWER switch of the PCR-LE slave 

units.

Even when you turn ON the POWER switches, the PCR-LEs 
do not turn on.

 

Turn ON the POWER switch of the PCR-LE master 

unit.

The PCR-LE slave units will also turn on.

- Note -

The power signal travels from the J2 connector to the J1 connec-
tor. Operating the POWER switch of the PCR-LE master unit will 
cause the other PCR-LEs to respond in sync.

POWER ON

Synchronized POWER ON

PCR–LE

 

„

Power OFF

When you turn off the POWER switch on the master unit, all slave 
units power off in sync.

Power OFF in an Emergency

In an emergency, turn OFF all POWER switches.

 

„

To Stop Synchronization

Set the POWER SELECTOR switches of all PCR-LEs to “MASTER”.

Operation Check

Check the operation of the PCR-LE series before you connect the 
load. Check the following items with no load connected. For detail 
of settings, see the PCR-LE series operation manual.

POWER switch ON
Voltage setting
OUTPUT ON/OFF
Voltage-range switching

If a trouble is occurring on even one unit, you will not be able to 
perform parallel operation.

Performing zero adjustment

When you perform master-slave parallel operation for the first time, 
current measurement offsets may appear in the current, power, 
power factor, and apparent power displays and the harmonic cur-
rent analysis values (minute values are displayed under no-load 
conditions). To perform accurate measurements, perform zero ad-
justment.
To perform even more accurate measurements, with no load con-
nected, wait 30 minutes after you turn the POWER switch on, and 
then perform zero adjustment.

 

Turn on the POWER switches on all PCR-LEs.

 

Configure the master unit as follows:

Output voltage mode: AC
Output voltage range: The desired range
AC voltage: 0 V

 

Turn on the output.

 

Press CONFIG (SHIFT+OPR MODE), 1/2 (F6), and 

then CURR ADJ (F5). Press the START (F1) key.

Zero adjustment starts.
When the zero adjustment is complete, "Measure Current 
ZERO Adjustment Finished" appears.

 

Press the OK (F4) key to end zero adjustment.

To adjust a different output voltage range, turn off the out-
put, change the output voltage range, and then repeat 
steps 3 to 5.

Once a zero adjustment is performed, as long as you do not 
change the connection, the PCR-LE remembers the calibration val-
ues for the master-slave parallel operation even when you turn off 
the POWER switch. If the ambient temperature changes, perform 
zero adjustment.

Содержание PCR-LE Series

Страница 1: ...nd accessories have not been damaged during transportation If the device is damaged or any accessory is missing notify Kikusui distributor agent Setup Guide This sheet 1pc PD05M PCR LE or PD05S PCR LE 1pc PD05M PCR LE only Protection sockets 2 pcs 84 49 0110 Connecting cable 70 cm 1pc 91 88 0180 Power signal cable 30 cm 1pc 91 88 0182 PD05S PCR LE only Functional limitations during paral lel opera...

Страница 2: ... panel 8 Follow the same procedure to install the other board This completes installation of the parallel board Connecting the Boards Use the master unit to control all the slave units It is convenient to place the master unit in an easy to operate location Use the connecting cables to connect between boards and the power signal cables to connect the PCR LEs Arrange the PCR LEs so that they are as...

Страница 3: ... J4 connectors are on the rear panel Insert the cable firmly into the connectors until the are locked in place PCR LE Power signal cable Power signal cable Power signal cable Master unit Slave unint Slave unit Example of three PCR LEs parallel control J2 J4 J1 J3 J2 J4 J1 J3 J2 J4 J1 J3 Locking tab Connect for J1 J2 connector Connect for J3 connector Locking tab Connect for J4 connector Locking ta...

Страница 4: ...n an Emergency In an emergency turn OFF all POWER switches To Stop Synchronization Set the POWER SELECTOR switches of all PCR LEs to MASTER Operation Check Check the operation of the PCR LE series before you connect the load Check the following items with no load connected For detail of settings see the PCR LE series operation manual POWER switch ON Voltage setting OUTPUT ON OFF Voltage range swit...

Страница 5: ...om the master unit The master unit displays the total output current of the system For details of settings see the operation manual included with the PCR LE series The screen captures used in the PCR LE series operation manual are examples They may differ from the screens that are displayed when you are setting parallel operation To Stop master slave parallel operation To quit master slave paralle...

Страница 6: ...对环境污染 人身 财产产生重大的影响 产品的废弃请遵守有关规定 产品的制造年月可以在以下网址中确认 http www kikusui co jp pi 毒有害物质或元素名称及含有标示 Name of hazardous materials and symbol of elemet in the equipment and quantity 有毒有害物质或元素 铅 Pb 汞 Hg 镉 Cd 六价铬 Cr VI 多溴联苯 PBB 多溴二苯醚 PBDE 本表格依据 SJ T 11364 的规定编制 该部件所有均质材料的有毒有害物质的含量不超过 GB T 26572 标准所规定的极 限值要求 该部件至少有一种均质材料的有毒有害物质的含量超过 GB T 26572 标准所规定 的极限值要求 ...

Отзывы: