PD05M-PCR-LE/PD05S-PCR-LE 3

Connecting PCR-LEs Together

First, connect PCR-LEs together with power signal cables. Then, 
connect the PCR-LE to the relay terminal board with output cables.

WARNING

Risk of electric shock. 

• Before you connect cables to the connectors/termi-

nals, be sure to turn the POWER switch off, and then 

remove the power plug from the outlet or turn off the 

switchboard.

• Do not use the terminal block with the terminal cover 

removed.

CAUTION

Risk of malfunction. 
• Do not reverse the L and N polarities.
• The thickness (cross-sectional area) of the output cables to 

be used for this connection should be the same as that of 

the output cables for one PCR-LE power supply.

- Note -
To acquire stable measurements, be sure to use a relay terminal 

board to connect the load. The length of the cable between the 

PCR-LE to the relay terminal board must be 1 m or less.

 

Check that the POWER switches of PCR-LEs are off.

 

With a power signal cable, connect the J2 connector 

of the master unit to the J1 connector of the slave 

unit and the J4 connector of the master unit to the J3 

connector of the slave unit.

The J1/ J2/ J3/ J4 connectors are on the rear panel
Insert the cable firmly into the connectors until the are 
locked in place.

PCR–LE

Power signal cable

Power signal cable

Power signal cable

Master unit

Slave unint

Slave unit

Example of three PCR-LEs parallel control

J2

J4

J1 J3

J2

J4

J1 J3

J2

J4

J1 J3

Locking tab

Connect for J1/ J2

connector

Connect for J3 connector

Locking tab

Connect for J4 connector

Locking tab

PCR–LE

Slave unit

Slave unit

Master unit

J2

J4

J1 J3

J2

J4

J1 J3

J2

J4

J1 J3

PCR–LE

Slave unit

Master unit

Slave unit

J2

J4

J1 J3

J2

J4

J1 J3

J2

J4

J1 J3

 

Connect all the remaining slave units in the same 

manner.

The signal flows from the J4 connector to the J3 connector 
and from the J2 connector to the J1 connector.
This completes connection.

 

Connect the PCR-LE output terminal to the relay ter-

minal board with output cables.

For detail of handling the terminal block tray, OUTPUT ter-
minal block, and load wire, see the PCR-LE series setup 
guide.
The PCR-LE Series OUTPUT terminal block is wired after 
you first pull out the terminal block tray. The terminal box 
covers ensure that you don’t touch the unwired terminals.

Bundle or twist 

two cables each.

The cable length should

be 1 m or less.

PCR–LE

OUTPUT

G N L

OUTPUT

G N L

OUTPUT

G N L

Relay terminal board

Example of the Parallel 

Connection of PCR-LE

N L

G

Содержание PCR-LE Series

Страница 1: ...nd accessories have not been damaged during transportation If the device is damaged or any accessory is missing notify Kikusui distributor agent Setup Guide This sheet 1pc PD05M PCR LE or PD05S PCR LE 1pc PD05M PCR LE only Protection sockets 2 pcs 84 49 0110 Connecting cable 70 cm 1pc 91 88 0180 Power signal cable 30 cm 1pc 91 88 0182 PD05S PCR LE only Functional limitations during paral lel opera...

Страница 2: ... panel 8 Follow the same procedure to install the other board This completes installation of the parallel board Connecting the Boards Use the master unit to control all the slave units It is convenient to place the master unit in an easy to operate location Use the connecting cables to connect between boards and the power signal cables to connect the PCR LEs Arrange the PCR LEs so that they are as...

Страница 3: ... J4 connectors are on the rear panel Insert the cable firmly into the connectors until the are locked in place PCR LE Power signal cable Power signal cable Power signal cable Master unit Slave unint Slave unit Example of three PCR LEs parallel control J2 J4 J1 J3 J2 J4 J1 J3 J2 J4 J1 J3 Locking tab Connect for J1 J2 connector Connect for J3 connector Locking tab Connect for J4 connector Locking ta...

Страница 4: ...n an Emergency In an emergency turn OFF all POWER switches To Stop Synchronization Set the POWER SELECTOR switches of all PCR LEs to MASTER Operation Check Check the operation of the PCR LE series before you connect the load Check the following items with no load connected For detail of settings see the PCR LE series operation manual POWER switch ON Voltage setting OUTPUT ON OFF Voltage range swit...

Страница 5: ...om the master unit The master unit displays the total output current of the system For details of settings see the operation manual included with the PCR LE series The screen captures used in the PCR LE series operation manual are examples They may differ from the screens that are displayed when you are setting parallel operation To Stop master slave parallel operation To quit master slave paralle...

Страница 6: ...对环境污染 人身 财产产生重大的影响 产品的废弃请遵守有关规定 产品的制造年月可以在以下网址中确认 http www kikusui co jp pi 毒有害物质或元素名称及含有标示 Name of hazardous materials and symbol of elemet in the equipment and quantity 有毒有害物质或元素 铅 Pb 汞 Hg 镉 Cd 六价铬 Cr VI 多溴联苯 PBB 多溴二苯醚 PBDE 本表格依据 SJ T 11364 的规定编制 该部件所有均质材料的有毒有害物质的含量不超过 GB T 26572 标准所规定的极 限值要求 该部件至少有一种均质材料的有毒有害物质的含量超过 GB T 26572 标准所规定 的极限值要求 ...

Отзывы: