Technical data sheet 1.10-51.110-81-en
DDC110-L1 .. DDC110-L4 technolon
®
Room Module
D e v i ce De s c ri p ti on
Operation DDC110-L4
Display depending on the configuration:
Room temperature (actual value) with function symbol
or
Room setpoint with function symbol
↕
Other function symbols can be displayed depending on the
configuration:
Day operation
Night operation
Standby operation
Automatic switchover by
Central Program or presence
detector
Function symbols
Digital readout
►
Room setpoint selection
The room setpoint for day, night or standby operation is automatically determined by the program.
Depending on the configuration release, the room setpoint can be raised or lowered by ± 3 K or ± 5 K by
manual adjustment.
The manual adjustment acts as setpoint correction for all operating modes alike:
Example:
If the current room setpoint day is raised by 2 K,
then the room setpoint night and the room setpoint standby are raised by 2 K .
Key
Press once : The Room Module switches to temperature type control setting.
Function symbols
↕
or
↕
or
↕
are displayed,
Simultaneously, the decimal place of the current control setting blinks .
Now the room setpoint can be increased or lowered with the key
in steps of 0.1 K .
With the key , it is immediately possible to switch back to the standard display.
Without pressing a key, the Room Module switches back to the standard after 5 sec
display . The new room setpoint is stored.
►
Switch on day or standby operation
The night or standby operation is automatically switched on or off by the Central Program.
The day operation is switched on by the presence detector or manually with the key
.
Switch on day operation
The day operation can only be switched on manually in the operation mode night or standby .
For the manual switching of night to day operation, the day operation is switched on only for a time period
determined by the program .
After expiration of this time, the Room Module switches back to night operation.
Switch on day operation
Press key
, function symbol
is displayed.
When switching over from night to day operation, the time period for switched on
day operation is displayed for 5 sec.
Standby
operation
The standby operation can be switched on by a presence detector or manually only in the daytime operation
mode, e.g. upon vacating the room.
Standby
operation
Press key , function symbol is displayed.
The key
switches off the standby operation again .
Page 8 / 12