Technical data sheet  1.10-51.110-81-en

 

DDC110-L1 .. DDC110-L4 technolon

®

 Room Module

 

D e v i ce   De s c ri p ti on

 

 

Technical data – Room Module DDC110-L1 to DDC110-L4

 

Mains 

24 V AC/DC ± 10 %, 10 mA (without I/O component UP) 

Bus connection 

- LON FTT10 

 

Application: According to LONMARK standard: 

 

 

LONMARK profile #8060 for single room control or 

 

 

LONMARK profile #8090 for room display and service module 

 

- Bus for I/O component UP on plug contact 

Measured variable 

Room temperature in residential and office space 

Measuring system 

integrated digital room sensor 

Measuring range 

0..45°C 

Connection 

Terminal connection, max, 2.5 mm

2

 

Display LCD 

display 

 

- Rough measured value 0..45.0°C, resolution 0.1 K 

 

- Room setpoint 0..45.0°C, resolution 0.1 K 

 

- Display icon for operating modes 

Control buttons 

DDC110-L1 

  Key, control setting of the room temperature 

 DDC110-L2 

 

Key, switchover to temperature type for setting the room setpoint 

 

 

  Key, switchover to ventilator modules for manual switching of the 

ventilator speeds 

 

 

  Key, setting the room setpoint or manual switching of the ventilator 

speeds backlighting of the keys 

 depending on the 

configuration:  

 

 

 

Steady burning light, on for 5 sec after keystroke, or backlighting off  

 DDC110-L3 

  Key, switchover to day operation 

 

 

 

Key, switchover to night or standby operation 

 

 

 

Key, switchover to temperature type for setting the room setpoint 

 

 

 

Backlighting of the keys 

 depending on the configuration: 

 

 

 

Steady burning light, on for 5 sec after keystroke or backlighting off  

 DDC110-L4 

  Key, switchover to day operation 

 

 

 

Key, switchover to night or standby operation 

 

 

 

Key, switchover to temperature type for setting the room setpoint 

 

 

 

Key, switchover to ventilator modules for manual switching of the 
ventilator speeds 

 

 

  Key, switchover to ventilator modules for manual switching of the 

ventilator speeds 

 

 

  Key, setting the room setpoint or manual switching of the ventilator 

speeds 

 

 

 

Backlighting of the keys 

 depending on the 

configuration: 

 

 

 

Steady burning light, on for 5 sec after keystroke or backlighting off  

Housing 

Hood, color RAL9010 (pure white) 

 

Special colors upon request 
Temperature 0..45°C, 

Ambient conditions 

Humidity not 

condensing 

Degree of enclosure 
protection 

IP30 

Dimensions 

Width x height x depth: 82.5 x 82.5 x 30 mm 

Assembly 

Wall mounted/assembly in flush-mounted box 

Weight 110 

 

 

Page 4 / 12 

Содержание Technolon DDC110-L1

Страница 1: ...ration and temperature type The DDC110 L4 technolon Room Module like DDC110 L3 additionally also has a user button for switching 3 ventilator speeds With an I O component accessory message inputs and...

Страница 2: ...tion Qualified specialists Every person using the devices shall have read and understood the descriptions in the technical data sheet If the equipment is not used according to the technical data sheet...

Страница 3: ...of the room temperature and manual adjustment of the room setpoint as well as switching of three ventilator speeds DDC110 L1 DDC110 L2 DDC110 L3 DDC110 L4 DDC110 L3 technolon Room Module with display...

Страница 4: ...tor speeds backlighting of the keys depending on the configuration Steady burning light on for 5 sec after keystroke or backlighting off DDC110 L3 Key switchover to day operation Key switchover to nig...

Страница 5: ...determined by the program Depending on the configuration release the room setpoint can be raised or lowered by 3 K or 5 K by manual adjustment The manual adjustment acts as setpoint correction for al...

Страница 6: ...ls or or are displayed Simultaneously the decimal place of the current control setting blinks Now the room setpoint can be increased or lowered with the key in steps of 0 1 K With the key it is immedi...

Страница 7: ...he decimal place of the current control setting blinks Now the room setpoint can be increased or lowered with the key in steps of 0 1 K Without pressing a key the Room Module switches back to the stan...

Страница 8: ...setting blinks Now the room setpoint can be increased or lowered with the key in steps of 0 1 K With the key it is immediately possible to switch back to the standard display Without pressing a key th...

Страница 9: ...mbol is displayed Simultaneously the current ventilator setting blinks 0 1 2 3 or auto 0 Ventilator off No function symbol 1 Ventilator level 1 on Function symbol 2 Ventilator level 2 on Function symb...

Страница 10: ...out by qualified personnel on voltage fee switched connecting leads Warning The Room Module can be mounted in the wall or in a flush mounted box For rapid and correct measurement of the room temperat...

Страница 11: ...ore pluggable hood inserts are a part of the delivery which can be exchanged for the standard inserts Note C1 D1 Inserts for higher air throughput D2 Inserts for cable inlet from below accessory kit w...

Страница 12: ...Room Module and the I O component UP is carried out on the 5 line bus line of the I O component which is connected with a socket plug on the Room Module Initial operation Warning Warning Supply volta...

Отзывы: