Valve Installation

!

CAUTION

The valve may only be installed by qualified technicians. In addition to the generally applicable instal-
lation guidelines, the following items are to be observed:

The pipeline system and the fixture interior must be free of foreign objects. In the event of contam-
inated media, dirt collectors are to be inserted upstream of the valves with fine screens, mesh width 
0.25 mm.

There must be no tension between the valve and the pipeline connection.

To avoid eddy formations in the valve body, the valve should be installed in a straight section of the 
pipe. A distance of 10 times the nominal diameter is recommended between the valve flange and 
manifold or other similar parts. 

The installation location is to be selected so that the ambient temperature at the actuator is kept 
between 0 °C–+50°C.

When carrying out installation, the permissible max. pressure difference 

p and the specified 

direction of flow must be observed (see table in "Types" section, as well as the "Valve Principle").

The three-way valves are to be used as mixing valves. Pay attention to the direction of flow (see 
fig. "Valve Principle").

Once the valve is installed, make sure the ball in the valve seating can be moved easily by pushing 
in the valve stem.

To install the actuator and remove the housing cover, approx. 170 mm of free space is required 
above the actuator. 

Observe the direction arrow on the valve body. Inverting the direction of flow impairs control 
behavior.

Содержание MD15-HE

Страница 1: ...sition or continuous control systems for zone post treatment devices for heating ventilation and air conditioning systems Content Page Important Information Regarding Product Safety 2 MD15 HE and MD15...

Страница 2: ...r to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who are familiar with...

Страница 3: ...5 mm2 Motor switch off Actuator spindle when extending load dependent when retracting path dependent Display LED display for operating voltage Actuating noise 28 dB A Positioning stroke 3 mm Position...

Страница 4: ...09 20 125 01 EN 2019 08 19 Dimensions Connection 86 5 48 5 60 51 75 M30x1 5 DIN 13 Continuous control M GY 24 V AC DC BU BN 0 V AC DC Y 0 2 10 V DC 1 2 3 MD15 HE GY 24 V AC DC BU BN 0 V AC DC Y 0 2 10...

Страница 5: ...HE MD15 R HE Product Description Q Page 5 14 3 09 20 125 01 EN 2019 08 19 Three point control Two point control GY 24 V AC DC BU BN 0 V AC DC M 1 2 3 MD15 HE GY 24 V AC DC BU BN 0 V AC DC M 1 2 3 MD1...

Страница 6: ...1 2 R20E 20 10 2 5 3 4 Straight through flow R10DV 10 10 0 86 3 8 with Kvs setting R15DV 15 10 0 86 1 2 R20DV 20 10 0 86 3 4 Flow through 90 R10EV 10 10 0 86 3 8 with Kvs setting R15EV 15 10 0 86 1 2...

Страница 7: ...The maximum flow rate Kvs value m h can be selected by using the settings 1 2 3 4 5 6 7 or 8 delivery setting 8 corresponds to a Kvs value 0 86 The setting can be made using a Z29 socket key accessor...

Страница 8: ...ce of 10 times the nominal diameter is recommended between the valve flange and manifold or other similar parts The installation location is to be selected so that the ambient temperature at the actua...

Страница 9: ...rential pressure builds up in the valve body before beginning work If necessary close the gate valve and turn off pumps After the pipeline has cooled off the actuator can be installed Be sure to compl...

Страница 10: ...ten hand tight using the union nut Establish the electrical connection After the line power has been switched on an automatic initialization run takes place The actuator first travels to the upper end...

Страница 11: ...ose the gate valve and turn off pumps After the pipeline has cooled off you can begin removing the actuator CAUTION Before beginning to remove the unit move the actuator to the uppermost position Remo...

Страница 12: ...ket 4 mm can be used to move the actuator into any position CAUTION If you manually adjust until the slip clutch responds turn the hexagon key half a turn in the opposite direction after the manually...

Страница 13: ...ing commissioning Valve exercise prevents the cone from jamming when the valve is not moved for a long period of inactivity e g for heating systems during the summer If valve exercise is activated the...

Страница 14: ...Product Description MD15 HE MD15 R HE Q Page 14 14 3 09 20 125 01 EN 2019 08 19...

Отзывы: