background image

A

Page 7 / 22

Datasheet 3.09-20.315-01-EN

MD15-FTL-HE, MD15-FTL-OV

Product Description

Issue 2017-01-09 Rev 1

Radio Interface

The communication with the radio partner is cyclical, bidirectional and includes intelligent reception/
transmission management.
Upon the first reception of the radio telegram (for teaching-in a radio partner, see page 19), the radio 
small actuator automatically adapts its operating mode according to the method of control from the 
radio partner (actuator mode or self-controlled mode).

NOTE

If the communication with the radio partner is disrupted, the “emergency mode” status bit 
(self-controlled mode) is set (can be evaluated for service diagnostics).
After the malfunction has been rectified (details can be found in the documentation of the radio 
partner), the radio partner is automatically resynchronized.

!

NOTICE

This product uses only EnOcean telegrams
When selecting a radio partner, ensure that the radio interface also works with the EnOcean telegram 
EEP A5-20-01 (Battery Powered Actuator).

Содержание MD15-FTL-HE

Страница 1: ...ntrol in heating systems The actuator is radio controlled based on the non proprietary EnOcean radio protocol The following EnOcean Equipment Profile EEP is supported EEP A5 20 01 Battery Powered Actu...

Страница 2: ...taller or operator to comply with local regulations Mounting installation and commissioning work on the devices may only be carried out by qualified technicians Qualified technicians are persons who a...

Страница 3: ...t settings Measuring system Integrated digital temperature sensor 0 40 C 0 5 C at 25 C Interfaces EnOcean radio interface Radio telegram EnOcean radio telegram bidirectional EEP A5 20 01 Battery Power...

Страница 4: ...no ID Type Z800 9703 24 Danfoss series 2 20 x 1 Z801 9704 24 Danfoss series 3 23 5 x 1 5 Z802 Danfoss RA2000 Z803 9800 24 Danfoss RAV Z804 9700 24 Danfoss RAV L Z805 9700 27 Vaillant 30 mm Z806 9701...

Страница 5: ...actual value and the integrated control function of the actuator With external operator panel EnOcean technology Using the operator panel the users can freely determine the setpoint or enter their ow...

Страница 6: ...the radio partner is checked Performing a communication test has no effect on the transmission reception interval see p 20 Energy block automatic Window open recognition When a window is open the flow...

Страница 7: ...ode according to the method of control from the radio partner actuator mode or self controlled mode NOTE If the communication with the radio partner is disrupted the emergency mode status bit self con...

Страница 8: ...N Bit 0b0 Teach in telegram 0b1 Data telegram DB_0 BIT_2 Self controlled mode 0b0 off 0b1 on DB_0 BIT_1 Not used DB_0 BIT_0 Not used Receive mode Commands from the controller to the actuator rx time m...

Страница 9: ...hroughput R10E 10 10 1 25 3 8 R15E 15 10 1 35 1 2 R20E 20 10 2 5 3 4 Straight throughput R10DV 10 10 0 73 3 8 with Kvs setting R15DV 15 10 0 73 1 2 R20DV 20 10 0 73 3 4 Right angled throughput R10EV 1...

Страница 10: ...mass flow rate The maximum flow rate Kvs value m h can be selected by using the settings 1 2 3 4 5 6 7 or 8 delivery setting 8 corresponds to a Kvs value 0 86 The setting can be made using a Z29 socke...

Страница 11: ...a straight section of the pipe A distance of 10 times the nominal diameter is recommended between the valve flange and manifold or other similar parts The installation location is to be selected so t...

Страница 12: ...tteries with the correct polarity When inserting the batteries observe the polarity as marked in the battery compartment Use only alkaline batteries type AA LR6 1 5 V NOTE After changing the batteries...

Страница 13: ...rtment cover using the special key supplied by inserting it into the intended place Remove the cover The special key is included with delivery of the small actuator Inserting the batteries and close t...

Страница 14: ...22 Product Description MD15 FTL HE MD15 FTL OV Datasheet 3 09 20 315 01 EN Issue 2017 01 09 Rev 1 Installing accessories Z800 to Z816 Z802 Z805 Z800 Z801 and Z806 816 ID 1 2 3 2 mm 4 5 6 7 8 ID 1 2 3...

Страница 15: ...efore beginning work If necessary close the gate valve and turn off pumps After the pipeline has cooled off you can begin removal of the small actuator MD15 FTL HE MD15 FTL OV Open the battery compart...

Страница 16: ...A Page 16 22 Product Description MD15 FTL HE MD15 FTL OV Datasheet 3 09 20 315 01 EN Issue 2017 01 09 Rev 1 Commissioning Overview of functions...

Страница 17: ...s and functions of the MD15 FTL xx In addition to these instructions the product descriptions of other system components such as radio partners are to be observed The buttons and LED displays that are...

Страница 18: ...ch in process was successful both visually status LED flashes green 2 times and acoustically 2 signal tones in succession An initialization run is automatically carried out Close the housing of the MD...

Страница 19: ...ion path NOTE If the communication with the radio partner is interrupted for longer than 1 h the radio small actuator switches to emergency mode see page 5 and the emergency mode status bit self contr...

Страница 20: ...hear 5 successive signal tones and the status LED flashes green 4 times and orange 1 time Release the push button 2 The new radio communication interval is acknowledged again both visually and acousti...

Страница 21: ...ver NOTICE Insert the batteries with the correct polarity When inserting the batteries observe the polarity as marked in the battery compartment Use only alkaline batteries type AA LR6 1 5 V NOTE Afte...

Страница 22: ...tteries in the household waste Dispose of used batteries at an approved collection point or store in accordance with legal regula tions or follow the applicable guidelines in your country for reducing...

Отзывы: