Commissioning
|
en:key
►
1
Press the “occupancy button” and the “setting button” simultaneously and
hold them down for 5 seconds.
“rEs” is displayed briefly.
The “Code
Δ
,” “Sun,” “Occupancy” and temperature icons appear.
The room sensor is switched on; the occupancy sensor and solar cell are
active.
2
Briefly press the “setting button” on the room sensor.
The “Antenna” icon flashes. The “Prog” icon appears.
The room sensor is ready to receive.
3
Within 15 seconds, briefly press the “registration button” on the valve
controller.
The valve controller acknowledges startup with one signal tone shortly
afterwards.
The valve controller acknowledges successful registration with two signal
tones.
Room sensor shows the number of registered valve controllers.
The “Antenna” icon appears permanently. The “Prog” icon disappears.
The “Code
Δ
” and “Sun” icons disappear after the first data exchange and the
“Auto” icon appears.
Pressing the “registration button” for longer, i.e., until your press is acknowl-
edged with a signal tone, switches the valve controller off. Registration was
not successful and must be repeated.
To register up to three additional valve controllers, briefly press the “registra-
tion button” of the next valve controller within 15 seconds.