background image

 

2 / 2 

 

P/N P-047550-1809-EN • REV 06 • ISS 10MAR16 

Figure 1: Tamper resist features 

 

(1)  Tamper-resist lever arm on base (break off to disable) 
(2)  Access slot for tamper-resist mechanism 

Specifications 

 
Voltage 

15.2 to 19.95 VDC 

Current 
 Normal 
 Alarm 
 Stand-alone 

alarm 

 
45 µA 
45 µA 
18 mA 

Air velocity 

0 to 5,000 ft./min (0 to 25.39 m/s) 

UL/ULC smoke 
sensitivity 

0.67 to 3.77%/ft. obscuration 

Environmental 
compensation 

Automatic 

Distance from ceiling 
(wall mounted) 

12 in. (305 mm) max. 

Compatible bases 
 Standard 
 Relay 
 Isolator 
 Audible 

 
GSA-SB, GSA-SB4 
GSA-RB, GSA-RB4 
GSA-IB, GSA-IB4 
GSA-AB4, GSA-AB4G, GSA-SBT, 
SIGA-AB4G-LF 

Operating environment 
 Temperature 
 Relative 

humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing 

Storage temperature 

4 to 140°F (

20 to 60°C) 

 