Page 11 of 17    Revision 1.1    Aug 2020

Document No. AlarmLine II Digital EN Controller Installation Instructions 

Commissioning (Cont.)

9. If “Yes” was selected in step 8, the AlarmLine II Digital EN Controller will 
then ask if the zone is ready to be calibrated. Ensure that the connection 
between the leader cable and/or the IS barriers and the 

start

 of the 

Digital LHD cable is securely shorted out between the two cores. When 
this is done, press the “Set” button to continue.

10. The AlarmLine II Digital EN Controller will display the voltage drop 
across the leader cable. If necessary, press “Select” to perform the 
calibration measurement again. The AlarmLine II Digital EN Controller will 
display the updated voltage drop in mV (milli-volts). The displayed value 
should be equal to approximately the loop resistance in ohms from the 
AlarmLine II Digital EN Controller, with the short in place, divided by 8. 
Once the voltage drop has been confirmed correct, press “Set” to continue. 

Now remove the short at the start of the LHD cable

.

11. If the Linear Heat Detection cable is connected directly to the 
AlarmLine II Digital EN Controller then select No and press the Set button 
to continue.

12. Select whether you would like the alarm outputs for both zones to  
be latching. If set to Yes, then 

if an alarm is triggered the unit will either 

require the power supply to be interrupted (min. 2s) or the Set button  
to be pressed to reset to normal once the alarm conditioned has  
been cleared.

13. Select whether the Modbus output should be enabled. If this is not 
enabled then proceed to step 17.

14. Select required Modbus type, either RTU or ASCII.

15. Set the Modbus address for this device (1-247).

16. Cycle through the possible Baud Rates for the Modbus RTU/ASCII 
output. (2400, 4800, 9600, 19200, 38400, 57600, 115200).

17. Select the number of data bits for the Modbus RTU/ASCII output. 
(7 or 8)

18. Select the number of stop bits for the Modbus RTU/ASCII output. 
(1 or 2).

19. Select the parity for the Modbus RTU/ASCII output. 
(even/odd/none).

Modbus TYPE
RTU

Modbus address
1

Latching outputs
No

Modbus output on
yes

Ready to
calibrate?

Zone 2 cal:
109 mV

ZONE 2  ldr cable
no

BAUD RATE
2400

DATA BITs
7

Stop BITs
1

PariTY
Even

Содержание Alarmline II Digital EN

Страница 1: ...2020 DocumentNo AlarmLineIIDigitalENControllerInstallationInstructions Page 1 of 17 Revision 1 1 Aug 2020 DocumentNo AlarmLineIIDigitalENControllerInstallationInstructions AlarmlineIIDigitalENControl...

Страница 2: ...tallation Page 6 Overview Connections Diagram Operating Modes Page 7 Wiring Diagram Independent Wiring Diagram Interlock Useful Information Page 9 Leader Cable Mounting Dimensions Static Discharge Cau...

Страница 3: ...d sufficient training on the unit Only use Kidde AlarmLine II Digital EN Linear Heat Detection cable with the AlarmLine II Digital EN Controller Test the Digital Linear Heat Detection cable before con...

Страница 4: ...The two zones can operate independently of each other or in interlock mode and a separate alarm and normally conducting fault output are provided for each zone The unit is intended to be installed bet...

Страница 5: ...c 36Vdc Current Consumption Normal Operation standby 15mA 7mA 5mA Alarm 40mA 23mA 15mA Operating Temperature Range 20 C 50 C 4 F 122 F Terminal Blocks Spacing 5mm Rising Clamp Rating 16A Wire Size 0 0...

Страница 6: ...The fault outputs also stop conducting on power loss to the unit or microprocessor fault triggering a fault at the fire alarm control panel The two wire RS 485 Modbus RTU ASCII output also outputs th...

Страница 7: ...erature Digital LHD cables Zone 1 250m Zone 2 120m Power supply 250m 120m NC NO C NC NO C Zone Switch IO Module Zone Switch IO Module Addressable loop Addressable loop RS 485 Modbus RTU A A EOL EOL Ju...

Страница 8: ...tion cables must be installed in each protected space See the AlarmLine II Digital EN LHD Installation Instructions for the linear spacing specification Zone 1 250m Zone 2 250m Power supply 250m NC NO...

Страница 9: ...vice The mounting holes are located adjacent to the lid screw positions Suitable screws for the type of wall the AlarmLine II Digital EN Controller is to be mounted on will need to be provided for sep...

Страница 10: ...s activate only when both Digital LHD zones trigger an alarm 6 Select the relevant operating programme for Zone 1 based on the table below 7 Select the relevant operating programme for Zone 2 based on...

Страница 11: ...start of the LHD cable 11 If the Linear Heat Detection cable is connected directly to the AlarmLine II Digital EN Controller then select No and press the Set button to continue 12 Select whether you...

Страница 12: ...whenAlarmLineIIDigitalENControllerisinnormaloperation Independentmode Interlockmode NormalOperation 20 Once the unit has been commissioned the display will show the zone status In normal operation th...

Страница 13: ...is in fault 24 The unit monitors for interference faults when the input may be changing between alarm ok and fault conditions for example too rapidly In this case an I F fault is displayed on the corr...

Страница 14: ...show ok The alarm relays will be o and the fault output normally conducting on 3 In self test mode and alarm condition the display will show alarm The alarm relays will be on After approx 8 seconds th...

Страница 15: ...ll respond in the following manner Number of bytes of register values to be read 8 bit Register values 16 bits per register The AlarmLine II Digital EN Controller stores the information for each zone...

Страница 16: ...10 seconds continuously While the SET and SELECT buttons are held down the power LED will flash quickly to confirm this procedure is about to take place After approximately 10 seconds the unit will r...

Страница 17: ...al state regardless of the state of the other zone Interlock mode The mode on the AlarmLine II Digital EN Controller where the alarm relay outputs will only activate when both Digital LHD cables go in...

Отзывы: