background image

listed household wire (18 gauge or larger as required by local codes) available at all electrical sup-
ply stores and most hardware stores.

FIGURE 1 INTERCONNECT WIRING DIAGRAM

WIRES ON ALARM HARNESS

CONNECTED TO

Black

Hot Side of A.C. Line

White

Neutral Side of A.C. Line

Red

Interconnect Lines (Red Wires) of Other 
Units in the Multiple Station Set up

BATTERY INSTALLATION

See Maintenance (Section 6) for battery installation

CAUTION! IF BOTH BATTERY REMINDER FINGERS ARE NOT HELD DOWN IN THE BATTERY
COMPARTMENT BY THE BATTERIES, THE BATTERY DOOR WILL NOT CLOSE, THE A.C. QUICK
CONNECTOR WILL NOT ATTACH TO THE ALARM, AND THE ALARM WILL NOT ATTACH TO THE
TRIM RING (SEE SECTION 6, FIGURE 6).

MOUNTING INSTRUCTIONS

CAUTION: THIS UNIT IS SEALED.  THE COVER IS NOT REMOVABLE!

1. Remove the trim ring from the back of the alarm by holding the trim ring and twisting the alarm in

the direction indicated by the “OFF” arrow on the alarm cover.

2. After selecting the proper smoke alarm location as described in Section 1 and wiring the A.C.

QUICK CONNECT harness as described in the WIRING INSTRUCTIONS, attach the trim ring to the
electrical box (see Figure 2).

3. Use a screwdriver to punch out only the pair of holes in the trim ring that match your type of elec-

trical box or plaster ring.  Mount the trim ring to the electrical box, using the appropriate holes.
NOTE:  Use the circle, square and octagon markings near each mounting hole in the trim ring to
help you select the correct mounting holes (see Figure 2).

4. Pull the A.C. QUICK CONNECTOR through the center hole in the trim ring and mount the ring,

making sure that the mounting screws are positioned in the small ends of the keyholes before
tightening the screws (see Figure 2).

5. Plug the A.C. QUICK CONNECTOR into the back of the alarm (see Figure 3), making sure that the

locks on the connector snap into place.  Then push the excess wire back into the electrical box
through the hole in the center of the trim ring.

Optional Accessory

2. LOCATIONS TO AVOID

• In the garage.  Products of combustion are present when you start your automobile.

• Less than 4” (10cm) from the peak of an “A” frame type ceiling.

• In an area where the temperature may fall below 40ºF or rise above 100ºF.

• In dusty areas.  Dust particles may cause nuisance alarms or failure to alarm.

• In very humid areas.  Moisture or steam can cause nuisance alarms.

• In insect infested areas.

• Smoke alarms should not be installed within 3 ft. (.9m) of the following: the door to a kitchen, the

door to a bathroom containing a tub or shower, forced air ducts used for heating or cooling, ceiling
or whole house ventilating fans, or other high air flow areas.

• Kitchens. Normal cooking may cause nuisance alarms. If a kitchen alarm is desired, it should have

an alarm silence feature or be a photoelectric type.

• Near fluorescent lights.  Electronic “noise” may cause nuisance alarms.

3. INSTALLATION INSTRUCTIONS

WIRING REQUIREMENTS

• This smoke alarm should be installed on a U.L. listed or recognized junction box.  All connections

should be made by a qualified electrician and must conform to article 760 of the U.S. National
Electrical Code, NFPA 72 and/or any other codes having jurisdiction in your area.

• The appropriate power source is 120 Volt A.C. Single Phase supplied from a non-switchable circuit

which is not protected by a ground fault interrupter.

WIRING INSTRUCTIONS FOR A.C. QUICK CONNECT HARNESS

CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT BEFORE WIRING THE ALARM.

• For alarms that are used as single station, DO NOT CONNECT THE RED WIRE TO ANYTHING.

Leave the red wire insulating cap in place to make certain that the red wire cannot contact any
metal parts or the electrical box.

• When alarms are interconnected, all interconnected units must be powered from a single circuit.

• A maximum of 24 Lifesaver devices may be interconnected in a multiple station arrangement.  The

interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18
alarms total (smoke, heat, etc.)  With 18 alarms interconnected, it is still possible to interconnect up
to a total of 6 remote signaling devices and/or relay modules.

• When mixing models which have battery backup (1275, 1275H, 1285, PE 120, HD135F) with

models without battery backup (1235, 120X, SL177i) be advised that the models without battery
backup will not respond during an AC power failure.

• The maximum wire run distance between the first and last unit in an interconnected system is

1000 feet.

• Figure 1 illustrates interconnection wiring.  Improper connection will result in damage to the alarm,

failure to operate, or a shock hazard.

• Make certain alarms are wired to a continuous (non-switched) power line.  NOTE: Use standard UL

Содержание 1285

Страница 1: ...n We know you expect noth ing less when the lives of your family are at stake For your convenience write down the following information If you call our Consumer Hotline these are the first questions you will be asked Smoke Alarm Model Number located on back of alarm Date Code located on back of alarm The National Fire Protection Association NFPA and the manufacturer recommends replacing this alarm...

Страница 2: ...rAdditionalProtection IonizationTypeSmokeAlarmswith Hush ControlorPhotoelectricType DIAGRAM B 3 ft 0 9m 3 ft 0 9m HORIZONTAL DISTANCE FROM PEAK ANYWHERE IN THIS AREA DIAGRAM C This product is designed to detect products of combustion using the ionization technique It contains 0 9 microcurie of Americium 241 a radioactive material Distributed under U S NRC License No 32 23858 01E Manufactured in co...

Страница 3: ...cles may cause nuisance alarms or failure to alarm In very humid areas Moisture or steam can cause nuisance alarms In insect infested areas Smoke alarms should not be installed within 3 ft 9m of the following the door to a kitchen the door to a bathroom containing a tub or shower forced air ducts used for heating or cooling ceiling or whole house ventilating fans or other high air flow areas Kitch...

Страница 4: ...the fuse or circuit breaker supplying power to the alarm circuit If the alarm still does not sound the unit has defective batteries or other failure DO NOT use an open flame to test your alarm you could damage the alarm or ignite combustible materials and start a structure fire TEST THE ALARM WEEKLY TO ENSURE PROPER OPERATION Erratic or low sound coming from your alarm may indicate a defective ala...

Страница 5: ...nd check for fires first If a fire is discovered get out and call the fire department If no fire is present check to see if one of the reasons listed in Section 2 may have caused the alarm 6 MAINTENANCE ALARM REMOVAL IF TAMPER RESIST PIN HAS BEEN USED REFER TO TAMPER RESIST LOCKING PIN IN SEC TION 3 FOR PIN REMOVAL INSTRUCTIONS To replace the batteries or the lamp remove the alarm from the trim ri...

Страница 6: ...arage is normally not recommended as these locations occasionally experience condi 7 LIMITATIONS OF SMOKE ALARMS WARNING PLEASE READ CAREFULLY AND THOROUGHLY NFPA 72 states Life safety from fire in residential occupancies is based primarily on early notification to occupants of the need to escape followed by the appropriate egress actions by those occu pants Fire warning systems for dwelling units...

Страница 7: ... allow the exclusion or limitation of incidental or consequential damages the above limitations or exclu sions may not apply to you While this warranty gives you specific legal rights you may also have other rights which vary from state to state Also KIDDE Safety makes no warranty express or implied written or oral including that of mer chantability or fitness for any particular purpose with respe...

Отзывы: