April 2003
76-100016-002
PEGAsys™ LV
4-4
1.
Isolate the agent release circuit (i.e., MP01 if used)
using the system menu (refer to Paragraph 2-5.4.1).
WARNING
!
Use safety precautions when removing
solenoid to prevent unwanted discharge or
activation.
2.
Physically remove the solenoid at the storage contain-
ers.
WARNING
!
The suppression system is now fully disarmed
from all automatic activation and, in some
cases, all manual activation.
3.
The system can now be tested without the risk of an
inadvertent release of agent.
4-4.2
Arming Release Circuit
Perform the following step-by-step procedure upon comple-
tion of system testing.
1.
Verify that the solenoid is disconnected from storage
container.
2.
Isolate the agent release circuit (i.e., MP01 if used)
using the system menu (refer to Paragraph 2-5.4.1).
3.
Ensure the system is free of any alarms to prevent
unwanted discharge or activation.
4.
Reconnect the solenoid at the storage container.
5.
De-isolate agent release circuit.
6.
The system is now in full operation in accordance with
system programming.
4-5
POWERING DOWN THE SYSTEM
4-5.1
Power-Down Procedure
The procedure to power-down the system is as follows:
1.
Ensure that the panel does not have any active alarms
to prevent unwanted discharge or activation.
CAUTION
!
If alarms do exist during power-down, power-
up of the panel will cause a reactivation of the
alarm sequence and possible activation of the
suppression system.
2.
Disarm release circuit as per Paragraph 4-4.1.
3.
Remove DC power first by disconnecting the batter-
ies.
4.
Remove AC power second by shutting off the circuit
breaker to the panel.
4-6
POWERING UP THE SYSTEM
4-6.1
Power-Up Procedure
1.
Ensure that the solenoid is disconnected from the stor-
age containers to prevent unwanted discharge or acti-
vation.
2.
If the system has been powered down, energize the
system by performing the following steps:
a.
Set the circuit breaker for the CCP power to ON.
Verify that the display reads "Main Processor
Power On". Ensure that the audible device is buzz-
ing continuously.
b.
Press the display module reset switch. Verify that
the audible device is silenced.
c.
Verify that the display reads as follows:
MAIN PROCESSOR
POWER ON
d.
After ten (10) seconds, verify that the display reads
as follows:
RXTX NON-MONITORING TROUBLE ON
RXTX1
e.
Verify that the POWER ON and TROUBLE indi-
cators are lit.
f.
Connect the backup batteries to the CCP in ac-
cordance to the procedure in Chapter 7.
g.
Press the <ACKLDGE> button. After approxi-
mately one minute the display for the RX/TX will
momentarily read:
RXTX NON-MONITORING TROUBLE OFF
h.
Verify the display reads the correct time and date.
If the incorrect time is displayed, perform step 2.i.
i.
Set time and date as follows:
aa. Press the zero (0) key. Verify that the display
reads:
PLEASE ENTER PASSWORD
bb. Type in the default first level password (987).
cc. Press the return (
↵
↵↵
↵↵
) key. Verify that the dis-
play reads:
1:ISOLATE
2:LIST
3:SET
4:TEST
dd. Type in 3111 on the keypad. Verify that the
display reads:
SYSTEM TIME (AM/PM)
ENTER THE TIME _ _ : _ _ (HH:MM)
ee. Type in the time (HH=hours 0-12 and then
MM=minutes 0-59). Press the return key.
Verify that the display reads:
Содержание PEGAsys LV
Страница 2: ......
Страница 4: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 15: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 22: ...1 6 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 28: ......
Страница 38: ...PEGAsys LV April 2003 76 100016 002 2 16 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 46: ...April 2003 76 100016 002 PEGAsys LV 3 8 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 52: ...April 2003 76 100016 002 PEGAsys LV 4 6 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 56: ...April 2003 76 100016 002 PEGAsys LV 5 4 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 66: ...April 2003 76 100016 002 PEGAsys LV 7 8 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 72: ...A 6 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 76: ...B 4 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 80: ...C 4 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 81: ...D 1 April 2003 76 100016 002 PEGAsys LV APPENDIX D SPACE RESERVED FOR FUTURE USE ...
Страница 82: ...D 2 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 84: ...E 2 April 2003 76 100016 002 PEGAsys THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 88: ...G 2 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 89: ...H 1 April 2003 76 100016 002 PEGAsys LV APPENDIX H SPACE RESERVED FOR FUTURE USE ...
Страница 90: ...H 2 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ...I 8 April 2003 76 100016 002 PEGAsys LV TITLE Installation Wiring Diagram Power Supply PEGAsys LV ...
Страница 119: ...N 1 April 2003 76 100016 002 PEGAsys LV APPENDIX N THIS SPACE RESERVED FOR FUTURE USE ...
Страница 120: ...N 2 April 2003 76 100016 002 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 122: ...O 2 April 2003 76 000000 001 PEGAsys LV THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 124: ...220423 KIDDE FENWAL Inc 400 Main Street Ashland MA 01721 Attn Documentation Manager Place Stamp Here FOLD FOLD ...
Страница 125: ......