Keysight Power Distribution Unit Installation Guide
10
General Installation Information
Use the following table to select the type of installation you are doing.
In the following tables, use the legend shown below to determine if the steps are
required for items A-F above:
Installation procedure
Columns in following
Installation Procedures tables
Type of PDU Installation
A
First PDU-Switched*
B
First PDU-Unswitched*
C
Second PDU-Switched (first one was also switched)
D
Second PDU-Unswitched (first one was switched)
E
Second PDU-Switched (first one was unswitched)
*
* Needs PDU Installation Kit
F
Second PDU-Unswitched (first one was also unswitched)
A shaded cell means the step applies.
A non-shaded cell means that the step does not apply.
Step
A
B
C
D
E
F
1
Turn off power to the rack and disconnect AC power.
Failure to disconnect AC power could result in a severe electric shock causing
injury or death.
When the remote switch is not utilized, the plug is considered to be the
disconnect device. When the plug is the disconnect device the socket-outlet
shall be installed near the equipment and shall be readily accessible.