Keysight Power Distribution Unit Installation Guide
PDU Specifications
PDU Specifications
The specifications for the customer orderable PDUs are given in the following
table:
Model
Number
E4451-67000
PDU for 1.3 M racks
E4453-67000
PDU for 1.3 M racks
E4455-67000
PDU for 1.6, 2.0 M
racks
E4457-67000
PDU for 1.6, 2.0 M
racks
Input
100-120V, 50/60
Hz
(N. America)
200-240V, 50/60 Hz
(International)
100-120V, 50/60 Hz
(N. America)
200-240V, 50/60 Hz
(International)
Output
100-120V, 50/60
Hz, 15A
1-IEC 320 C13
Receptacle
5-NEMA 5-15R
Receptacles
200-240V, 50/60 Hz,
15A
6-IEC 320 C13
Receptacles
100-120V, 50/60 Hz,
15A
1-IEC 320 C13
Receptacle
9-NEMA 5-15R
Receptacles
200-240V, 50/60 Hz,
15A
1-IEC 320 C19
Receptacle
10-IEC 320 C13
Receptacles
Operating
Temperature
0° C to 40° C
0° C to 40° C
0° C to 40° C
0° C to 40° C
Operating Humidity 5% to 80% RH,
non-condensing
5% to 80% RH,
non-condensing
5% to 80% RH,
non-condensing
5% to 80% RH,
non-condensing
Operating
Environment
Indoor Location
Indoor Location
Indoor Location
Indoor Location
Input
100-120V, 50/60
Hz
(N. America)
200-240V, 50/60 Hz
(International)
100-120V, 50/60 Hz
(N. America)
200-240V, 50/60 Hz
(International)
100-120V, 50/60 Hz PDUs (E4451-67000 and E4455-67000) are supplied with a
power cord terminated with a NEMA 5-20P plug to fit a 20A receptacle.
200-240V, 50/60 Hz PDUs (E4453-67000 and E4457-67000) are supplied
without a power plug—the PDU power cord is un-terminated. The installer must
install the correct plug for the country of installation.
All PDUs (100-120V or 200-240V) must be connected to a dedicated 20A
circuit.