Appendix B Using the Digital Port
108
Keysight N6700 User’s Guide
Fault/Inhibit System Protection
The following figure illustrates some ways that you can connect the
Fault/Inhibit pins of the connector.
As shown in the figure, when the Fault outputs and Inhibit inputs of
several mainframes are daisy-chained, an internal fault condition in one
of the mainframes will disable all of them without intervention by either
the controller or external circuitry.
You can also connect the Inhibit input to a manual switch or external
control signal that will short the Inhibit pin to common whenever it is
necessary to disable all output channels in the mainframe. Negative
polarity must be programmed for all pins in this case. You can also use
the Fault output to drive an external relay circuit or signal other devices
whenever a user-definable fault occurs.
Clearing a System Protection Fault
To restore all instruments to a normal operating condition when a fault
condition occurs in a daisy-chained system protection configuration, two
fault conditions must be removed:
1.
The initial protection fault or external Inhibit signal.
2.
The subsequent daisy-chained fault signal (which is sourced by
the Inhibit signal).
NOTE
Even when the initial fault condition or external signal is removed, the
Inhibit fault signal is still active and will continue to shut down the
outputs of all the mainframes.
To clear the daisy-chained fault signal if the operating mode of the
Inhibit input is Live, simply clear the output protection on any
ONE
mainframe as explained in chapter 4. If the operating mode of the Inhibit
input is Latched, turn off the Inhibit input on
ALL
mainframes individually.
To re-enable the chain, re-program the Inhibit input on each mainframe
to Latched mode.
Output State
Only pins 4 through 7 can be configured to control the output state. This
function lets you connect multiple Keysight N6700 mainframes together
and synchronize the output on/off sequence across mainframes. Refer to
Appendix D for detailed information.
Panic
switch
INH
Common
INH
Input
FLT INH
1 2 3 4 5 6 7
I
1 2 3 4 5 6 7
I
1 2 3 4 5 6 7
I
FLT INH
FLT INH
+ -
+ -
+ -