Remark!
Browse to the polyx to see the version information. For more information about
the versions, s
ee the KP_Install_update_Polyx manual.
3.2.1
Direct connection (RS485)
Recommended cable type between a Polyx and the Sirius card reader is: (see chapter 4.1 for
more information)
CAT5 UTP four twisted pairs of 24AWG copper conductors
CAT6 UTP four twisted pairs of 24AWG copper conductors
A direct connection (without using an Adapterboard) between the Sirius card reader and a
Polyx™ is
NOT
possible when:
Sirius and Polyx™ are installed in different buildings and thus the connection
leaves the building
or
the wiring is no UTP cable (CAT5 or CAT6)
or
an existing (non UTP) cable is reused
or
overvoltage protection for the card reader is required
or
An external power supply is required for the card reader.
If any of the above conditions applies, see section 3.2.2.
Polyx, directly connected to a Sirius card reader:
Picture T-568B
Pin number RJ-
45 Plug
Polyx™ PRT 2/3
TIA/EIA-568-B
Cable color
Signal
Connection
Sirius i30 card
reader
1
White/orange
B
2
2
Orange
A
1
3
White/green
B
2
4
Blue
Vcc (+)
7
5
White/blue
6
Green
A
1
7
White/brown
8
Brown
GND (-)
6