3.3. ALARMS.
RK-2006LSP controller continually checks operations of installed devices as well
as alarm sensors. In case of failure, the device activates alarm and proper
operations are carried out. Information on the problem is also shown on the display.
In addition depending on nature of damage the inner sound alarm system may be
activated. To cancel alarm, first identify the cause and repair it and then STOP
button shall be pressed. If alarm is cancelled and required repairs did not follow,
sound alarm system will be turned off only. In case more than one alarm has been
activated, information on each alarm will be displayed alternately.
Out of fuel alarm.
If in IGNITION mode the controller fails to detect a flame within the time specified
by the technician, „Out of fuel alarm” will be activated. To turn on the controller again
first refill fuel, cancel the alarm with STOP button and begin setting-up process by
pressing START button.
A L A R M :
O U T O F
F U E L
Emergency alarm.
Depending on construction type, the boiler may be equipped with emergency
sensor (e.g. hopper cover sensor). Activation of the alarm will result in fan and auger
turning off, and switching the controller into STAND-BY mode.
A L A R M :
E M E R G E N C Y
I N P U T
CAUTION!
This alarm does not result in engagement of inner sound system and
does not require cancelling. Once the hopper cover is closed, the programmed
process will be carried out from the moment when it was interrupted (it returns to the
mode that was before alarm activation).
Auger ignition alarm.
If the auger has been equipped with a temperature sensor, and the programmed
setting of „Auger ignition temperature" was exceeded, it will result in activation of
auger ignition alarm. The controller will go to SHUT DOWN mode.
A L A R M :
A U G E R
I G N I T I O N
CAUTION!
This alarm may be cancelled only if the auger temperature drops below
set point. If the alarm was cancelled before extinction completion, only sound alarm
will be turned off.
B O I L E R
T E M P .
6 0 c
A U G E R
E X T I N C T .