Configuration / Set-up menu
43 / 148
2018/02
1.6
Parameters
1.6.1
On delay
s
0 - 99
1.6.2
Run-on time
s
0 - 99
1.6.3
Max. Current
A
3.5 - 9.5
1.6.4
Min. Current
A
0.5 - 2.5
1.6.5
Limit number of operations
#/10min
1 - 99
1.6.6
Limit running time
min
1 - 999
1.6.7
Air bubbling offset
mm
0 - 99
1.6.8
Height of immersion pipe
mm
0 - 999
1.6.9
SDS Self diagnosis system
d
1 - 180
1.6.10
Measuring range level probe
mm
0 - 9999
1.6.11
On 1 - level
mm
0 - 5000
1.6.12
Off 1 - Level
mm
0 - 5000
1.6.13
Alarm level
mm
0 - 5000
1.6.14
On 2 - level
mm
0 - 5000
1.6.15
Off 2 - Level
mm
0 - 5000
1.6.16
On delay flap
s
0 - 99
1.6.17
Post run time flap
s
0 - 99
1.6.18
Max. current flap
mA
150 - 200
1.6.19
S1/S3 Pump operation
S1 operation/S3
operation
2
Maintenance
2.1
Manual operation
2.1.1
Pump 1
2.1.2
Potential-free contact
2.1.3
Ext. audible alarm
2.1.4
Communication
2.1.5
Pump 2
2.1.6
Flap
2.1.7
AC output
2.1.8
DC output
2.2
Automatic operation
2.2
Automatic operation
On Off
2.3
SDS Self diagnosis system
2.3.1
“Test pump I
Test battery
Test pump II
Test flap”
OK Fault
2.4
Maintenance due
2.4.1
Last maintenance
mm:hh - dd.mm.yy
2.4.2
Next maintenance
mm:hh - dd.mm.yy
2.5
Maintenance done
2.6
Maintenance interval
2.6.1
3 months
2.6.2
6 months
2.6.3
12 months
2.6.4
Manual maintenance intervals entry
2.6.5
No maintenance interval
2.7
Clearance remote control
2.7.1
Clearance duration
2.7.2
Deactivate
2.8
Calibration of pressure sensor
3
Settings
3.1
Parameters
3.1.1
On delay
s
0 - 99
3.1.2
Run-on time
s
0 - 99
3.1.3
Max. Current
A
3.5 - 9.5
3.1.4
Min. Current
A
0.5 - 2.5
3.1.5
Limit number of operations
#/10min
1 - 99
3.1.6
Limit running time
min
0 - 999
3.1.7
Air bubbling offset
mm
0 - 99
3.1.8
Height of immersion pipe
mm
0 - 999