background image

HSF (M) 300W 042315

15

5.1

ADJUSTING THE VOLTAGE 

NOTE: Refer to the RA 19-4C Rack Adapter manual for alternatives to the standard master/

slave parallel configuration described below.

To adjust the paralleled units, turn off all the units except one (designated as the master) and
adjust to desired voltage using the front page trimmer and monitoring the front panel voltmeter. 

Each slave must be adjusted to a slightly lower voltage than the previous unit. The differ-
ence between the master and the lowest voltage slave must not exceed 2% of E

NOM

The voltage separation between master and subsequent slave(s) (V

SEP

) = 2% E

NOM

 / N

where N = number of units in parallel. 

Adjust the first slave V

SLAVE1

 to E

NOM

 - V

SEP

. Adjust the second slave V

SLAVE2

 to V

SLAVE1

 -   V

SEP

.

Adjust the third slave V

SLAVE3

 to V

SLAVE2

 - V

SEP

 and so on.

As an example, for three HSF 24-27M units in parallel, 2% of E

NOM

 is 0.48V and V

SEP

 is 0.48/3 =

0.16V. Turn off the master, then turn on another unit (slave 1) and adjust for 160mV less than the
master. Turn off slave 1 and turn on slave 2 and adjust for 160mV less than slave 1.

When all units are turned on, the unit adjusted to the highest voltage will be the master. The
meters of all units read the voltage on the bus. If a unit fails, the VDC ON indicator of that unit is
either off or red, however the meter of a failed MZ Model may continue to read the voltage on the
bus since it is powered by a separate internal power supply.

5.2

PARALLEL CONNECTIONS, M MODELS

When using parallel-connected M Models, a minimum load is required to avoid the slave becom-
ing “idle.” When the slave is idle, the output is off, no lights are lit, and the alarm is set. The mini-
mum load (Amperes) = N x (I/10) where N = the number of units in parallel, I = Nominal current
rating of individual power supply (Amperes). For applications requiring either no load or lower
than minimum load conditions, the MZ Models are recommended.

5.3

PARALLEL CONNECTIONS, MZ MODELS

If parallel-connected MZ models are controlled individually, either a minimum load or voltage set
restrictions are required to avoid slave “idle” or slave “oscillating output” conditions; the idle and
oscillating output conditions show slightly different indications depending on the position of SW1
position 7 as defined below. 

NOTE: If the minimum load is maintained, voltage set restric-

tions are not required. 

If position 7 of SW1 is set to off (default, see PAR. 3.1), the VDC ON indicator is powered from the
output; therefore when a slave is idle, the output is off, VDC ON is off, and the alarm is set. The
oscillating output condition means that the unit alternates between briefly idle and output on (the
VDC ON indicator will appear dim as it goes on and off, and the toggling relay will be audible).

If position 7 of SW1 is set to on (see PAR. 3.1) so that the VDC ON indicator is powered from the
internal power supply, when a slave is idle, the output is off, VDC ON lights red, and the alarm is
set. The oscillating output condition means that the unit alternates between briefly idle and output
on (the VDC ON indicator will toggle between briefly amber and green, and the toggling relay will
be audible).

Содержание HSF 15-22M

Страница 1: ...and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without no...

Страница 2: ...onnecting Multiple Power Supplies 14 5 1 Adjusting the Voltage 15 5 2 Parallel Connections M Models 15 5 3 Parallel Connections MZ Models 15 5 3 1 Minimum Load 16 5 3 2 Voltage Set Restrictions 16 1 H...

Страница 3: ...out this manual where there are differences between M and MZ models refer to the MZ model information for HSF 5 60M The HSF M Models except for HSF 5 60M use the HSF output to power the VDC ON indicat...

Страница 4: ...AR 3 8 2 1 AL COM 14 Common contact of alarm relay see PAR 3 8 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one vol...

Страница 5: ...02 Unless otherwise noted specifications apply to both M and MZ models 1 M Models only To adjust output voltage down to approximately 0V use external voltage source or resistance see PAR 3 4 2 Refer t...

Страница 6: ...ximum Stabilization Source Effect min max 0 1 Typical 0 2 Maximum 85 to 132V a c 170 to 265V a c Load Effect 0 3 Typical 2 Maximum default 0 3 Typical 0 6 Maximum see PAR 3 4 Individual Mode 0 100 loa...

Страница 7: ...0 RoHS Compliance Contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B EN55022 B EMC Emission Radiated Designed to meet FCC Class B VC...

Страница 8: ...ront panel reset button to be used to reset the unit after a fault or allow Remote on off via mechanical switch or logic level see PAR 3 4 3 Positions 5 and 6 allows alarm signals to be produced from...

Страница 9: ...that overcurrent or overvoltage protection has tripped or thermal overload or fan malfunction has occurred If remote voltage control see PAR 3 4 2 is not enabled the front panel Vadj trimmer see PAR...

Страница 10: ...set to A to show output current V indicator Lights green to indicate meter is showing Volts A indicator Lights amber to indicate meter is showing Amperes FIGURE 5 FRONT PANEL CONTROLS INDICATORS AND...

Страница 11: ...For M Models except HSF 5 60M only To ensure proper operation of the alarm relay meter and LED indicators do not adjust external voltage below minimum listed in Table 4 Connect the voltage source acro...

Страница 12: ...se to reduce output voltage then reset the unit 3 5 REMOTE ON OFF When power is ON at the source the output may be turned ON or OFF using the RC signals if the remote ON OFF feature is enabled Note th...

Страница 13: ...e following protection features are implemented in the HSF 300W Series M and MZ Models overvoltage and overtemperature PAR 3 7 1 overcurrent PAR 3 7 2 fan failure PAR 3 7 3 and undervoltage PAR 3 7 4...

Страница 14: ...N ALARM indicator can be configured to light red if the respective power supply output voltage is lost or if the POWER switch is set to OFF This is enabled when DIP switch 1 position 8 set to ON This...

Страница 15: ...s nor mally conducting When the alarm is activated upon detection of power loss overvoltage fan fault overtemperature or overcurrent condition the transistor cuts off and the collector emitter cir cui...

Страница 16: ...up or down to ensure full engagement and disengagement of the latching mechanism When the HSF power supply is not installed in its plug in rack adapter it is recommended that the latch be secured in t...

Страница 17: ...LS When using parallel connected M Models a minimum load is required to avoid the slave becom ing idle When the slave is idle the output is off no lights are lit and the alarm is set The mini mum load...

Страница 18: ...n redundant mode with load less than 10 per unit For loads less than 10 voltage stabilization may be affected if units are turned off and on via the front panel causing voltage on the paralleled bus t...

Отзывы: