“high” and 0.0 to 0.4V “low”), or a contact closure. When the ±RC pins are open, using either a
mechanical switch or a high level logic signal, the HSF output is cut OFF. When the ±RC pins are
shorted, the output returns to within specifications. At low level logic, the maximum source current
is 1.6mA and at high level the sink current is 1.0mA. Positions 3 and 4 of both DIP switches must
be restored to the factory default setting (Figure 9A) if remote ON-OFF is not used. The ±RC pins
are isolated from DC output pins and a-c input terminals.

FIGURE 9.  DIP SWITCH SETTINGS FOR USING RESET BUTTON OR REMOTE ON-OFF

3.6

RESET (RESTART)

There are three ways to reset the unit:

If remote on/off feature (see PAR. 3.4.3) IS NOT in use, press and release the OUTPUT
RESET switch on the front panel. 

If the remote on/off feature IS in use (see PAR. 3.4.3), open the connection between the
±RC pins and then reconnect the pins. 

The unit may also be restarted by turning the POWER ON/OFF switch to OFF, waiting
40 seconds, then setting the POWER switch to ON.

3.7

PROTECTION CIRCUITS

The following protection features are implemented in the HSF 300W Series M and MZ Models:
overvoltage and overtemperature (PAR. 3.7.1), overcurrent (PAR. 3.7.2), fan failure (PAR. 3.7.3),
and undervoltage (PAR. 3.7.4). The HSF provides a configurable visual alarm (see PAR. 3.8.1) as
well as an option to use either relay contacts or logic levels for alarm signals (see PAR. 3.8.2) 

3.7.1 OVERVOLTAGE AND OVERTEMPERATURE PROTECTION

When the output voltage of the HSF increases beyond the specified values (see Table 2), the out-
put is cut OFF and the fan turns OFF. After shut down, reset (restart) the unit per PAR. 3.6.

When the internal temperature of the HSF increases beyond allowable limit, the output is cut OFF
and the fans turn OFF. The restart cycle (Power ON) should not begin until the temperature
returns to within specifications. To restart (reset) the unit, set the POWER ON/OFF switch to OFF,
wait until unit cools, then set the POWER switch to ON. The power supply cannot be reset using
the remote ON-OFF feature unless the power supply remains shut down for at least 40 seconds.

3042877

3

3  +RC

+RC  3

3

SW1

-RC  4

4

SW2

4

4  -RC

OFF

ON

OFF

ON

(FACTORY DEFAULT)

USE FRONT PANEL

RESET BUTTON

A

B

(LOGICAL LEVEL OR 

MECHANICAL SWITCH)

USE REMOTE ON-OFF

3

3

SW2

SW1

4

4

ON

OFF

OFF

ON

3  +RC

4  -RC

+RC  3

-RC  4

TAB

Содержание HSF 15-22M

Страница 1: ...and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without no...

Страница 2: ...onnecting Multiple Power Supplies 14 5 1 Adjusting the Voltage 15 5 2 Parallel Connections M Models 15 5 3 Parallel Connections MZ Models 15 5 3 1 Minimum Load 16 5 3 2 Voltage Set Restrictions 16 1 H...

Страница 3: ...out this manual where there are differences between M and MZ models refer to the MZ model information for HSF 5 60M The HSF M Models except for HSF 5 60M use the HSF output to power the VDC ON indicat...

Страница 4: ...AR 3 8 2 1 AL COM 14 Common contact of alarm relay see PAR 3 8 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one vol...

Страница 5: ...02 Unless otherwise noted specifications apply to both M and MZ models 1 M Models only To adjust output voltage down to approximately 0V use external voltage source or resistance see PAR 3 4 2 Refer t...

Страница 6: ...ximum Stabilization Source Effect min max 0 1 Typical 0 2 Maximum 85 to 132V a c 170 to 265V a c Load Effect 0 3 Typical 2 Maximum default 0 3 Typical 0 6 Maximum see PAR 3 4 Individual Mode 0 100 loa...

Страница 7: ...0 RoHS Compliance Contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B EN55022 B EMC Emission Radiated Designed to meet FCC Class B VC...

Страница 8: ...ront panel reset button to be used to reset the unit after a fault or allow Remote on off via mechanical switch or logic level see PAR 3 4 3 Positions 5 and 6 allows alarm signals to be produced from...

Страница 9: ...that overcurrent or overvoltage protection has tripped or thermal overload or fan malfunction has occurred If remote voltage control see PAR 3 4 2 is not enabled the front panel Vadj trimmer see PAR...

Страница 10: ...set to A to show output current V indicator Lights green to indicate meter is showing Volts A indicator Lights amber to indicate meter is showing Amperes FIGURE 5 FRONT PANEL CONTROLS INDICATORS AND...

Страница 11: ...For M Models except HSF 5 60M only To ensure proper operation of the alarm relay meter and LED indicators do not adjust external voltage below minimum listed in Table 4 Connect the voltage source acro...

Страница 12: ...se to reduce output voltage then reset the unit 3 5 REMOTE ON OFF When power is ON at the source the output may be turned ON or OFF using the RC signals if the remote ON OFF feature is enabled Note th...

Страница 13: ...e following protection features are implemented in the HSF 300W Series M and MZ Models overvoltage and overtemperature PAR 3 7 1 overcurrent PAR 3 7 2 fan failure PAR 3 7 3 and undervoltage PAR 3 7 4...

Страница 14: ...N ALARM indicator can be configured to light red if the respective power supply output voltage is lost or if the POWER switch is set to OFF This is enabled when DIP switch 1 position 8 set to ON This...

Страница 15: ...s nor mally conducting When the alarm is activated upon detection of power loss overvoltage fan fault overtemperature or overcurrent condition the transistor cuts off and the collector emitter cir cui...

Страница 16: ...up or down to ensure full engagement and disengagement of the latching mechanism When the HSF power supply is not installed in its plug in rack adapter it is recommended that the latch be secured in t...

Страница 17: ...LS When using parallel connected M Models a minimum load is required to avoid the slave becom ing idle When the slave is idle the output is off no lights are lit and the alarm is set The mini mum load...

Страница 18: ...n redundant mode with load less than 10 per unit For loads less than 10 voltage stabilization may be affected if units are turned off and on via the front panel causing voltage on the paralleled bus t...

Отзывы: