10

HSF (M) 300W 042315

FIGURE 7.  CONNECTIONS FOR REMOTE VOLTAGE CONTROL

3.4.3 VDC ON/ALARM INDICATOR POWER OPTIONS

To use the internal power supply reference voltage to power the VDC ON/ALARM indicator, set
Position 7 of SW1 to ON and Position 8 of SW2 to OFF (default) (see Figure 8A). Load effect is
±1% maximum. To use the HSF output voltage to power the VDC ON/ALARM indicator, set Posi-
tion 7 of SW1 to OFF and Position 8 of SW2 to ON (see Figure 8B). Load effect is ±0.6% maxi-
mum, however the minimums specified in Table 5 must be observed for the indicator to function.

FIGURE 8.  DIP SWITCH SETTINGS FOR VDC ON/ALARM POWER OPTIONS

Table 5 lists the minimum HSF output voltage required to maintain VDC ON indicator function for
this case. Maximum output voltage of unit might cause overvoltage trip if SW2, position 8 is
enabled. If this occurs, turn Vadj trim pot counterclockwise to reduce output voltage, then reset the
unit. 

3.5

REMOTE ON-OFF

When power is ON at the source, the output may be turned ON or OFF using the ±RC signals if
the remote ON-OFF feature is enabled. Note that when remote ON-OFF is enabled, the RESET
OUTPUT switch does not function. Remote ON-OFF is enabled by setting DIP switch positions 3
and 4 as shown in Figure 9B. The +RC and –RC signals (at the rack adapter I/O connector, pins
15 and 8, respectively) then turn the unit on or off. These pins accept a logic level (2.4V to 24V

TABLE 5.  CONDITIONS FOR VDC ON/ALARM LED OPERATION POWERED BY 

OUTPUT

MODEL 

HSF 5-60M

HSF 12-53MZ

HSF 15-43MZ

HSF 24-27MZ

HSF 28-23MZ

HSF 48-13MZ

Minimum HSF output voltage 
required for VDC ON   LED to 
function when SW 2 position 8 is 
ON and SW 1 position 7 is OFF 
(Volts d-c).

3.3

3.3

3.5

4.5

5

8

3043492

7

7 DC ON PWR BY REF

7

SW1

8

SW2

8

OFF

ON

OFF

ON

USE REFERENCE SUPPLY

(FACTORY DEFAULT)

TO POWER "DC ON"

A

TO POWER "DC ON"

USE HSF OUTPUT VOLTAGE

B

(REQUIRES MINIMUM OUTPUT VOLTAGE)

7
8

8

SW1

7

SW2

OFF

ON

ON

OFF

DC ON PWR BY OUTPUT V 8

8

7

7
8

8

7

TAB

Содержание HSF 15-22M

Страница 1: ...and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without no...

Страница 2: ...onnecting Multiple Power Supplies 14 5 1 Adjusting the Voltage 15 5 2 Parallel Connections M Models 15 5 3 Parallel Connections MZ Models 15 5 3 1 Minimum Load 16 5 3 2 Voltage Set Restrictions 16 1 H...

Страница 3: ...out this manual where there are differences between M and MZ models refer to the MZ model information for HSF 5 60M The HSF M Models except for HSF 5 60M use the HSF output to power the VDC ON indicat...

Страница 4: ...AR 3 8 2 1 AL COM 14 Common contact of alarm relay see PAR 3 8 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one vol...

Страница 5: ...02 Unless otherwise noted specifications apply to both M and MZ models 1 M Models only To adjust output voltage down to approximately 0V use external voltage source or resistance see PAR 3 4 2 Refer t...

Страница 6: ...ximum Stabilization Source Effect min max 0 1 Typical 0 2 Maximum 85 to 132V a c 170 to 265V a c Load Effect 0 3 Typical 2 Maximum default 0 3 Typical 0 6 Maximum see PAR 3 4 Individual Mode 0 100 loa...

Страница 7: ...0 RoHS Compliance Contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B EN55022 B EMC Emission Radiated Designed to meet FCC Class B VC...

Страница 8: ...ront panel reset button to be used to reset the unit after a fault or allow Remote on off via mechanical switch or logic level see PAR 3 4 3 Positions 5 and 6 allows alarm signals to be produced from...

Страница 9: ...that overcurrent or overvoltage protection has tripped or thermal overload or fan malfunction has occurred If remote voltage control see PAR 3 4 2 is not enabled the front panel Vadj trimmer see PAR...

Страница 10: ...set to A to show output current V indicator Lights green to indicate meter is showing Volts A indicator Lights amber to indicate meter is showing Amperes FIGURE 5 FRONT PANEL CONTROLS INDICATORS AND...

Страница 11: ...For M Models except HSF 5 60M only To ensure proper operation of the alarm relay meter and LED indicators do not adjust external voltage below minimum listed in Table 4 Connect the voltage source acro...

Страница 12: ...se to reduce output voltage then reset the unit 3 5 REMOTE ON OFF When power is ON at the source the output may be turned ON or OFF using the RC signals if the remote ON OFF feature is enabled Note th...

Страница 13: ...e following protection features are implemented in the HSF 300W Series M and MZ Models overvoltage and overtemperature PAR 3 7 1 overcurrent PAR 3 7 2 fan failure PAR 3 7 3 and undervoltage PAR 3 7 4...

Страница 14: ...N ALARM indicator can be configured to light red if the respective power supply output voltage is lost or if the POWER switch is set to OFF This is enabled when DIP switch 1 position 8 set to ON This...

Страница 15: ...s nor mally conducting When the alarm is activated upon detection of power loss overvoltage fan fault overtemperature or overcurrent condition the transistor cuts off and the collector emitter cir cui...

Страница 16: ...up or down to ensure full engagement and disengagement of the latching mechanism When the HSF power supply is not installed in its plug in rack adapter it is recommended that the latch be secured in t...

Страница 17: ...LS When using parallel connected M Models a minimum load is required to avoid the slave becom ing idle When the slave is idle the output is off no lights are lit and the alarm is set The mini mum load...

Страница 18: ...n redundant mode with load less than 10 per unit For loads less than 10 voltage stabilization may be affected if units are turned off and on via the front panel causing voltage on the paralleled bus t...

Отзывы: