background image

12

HSF(A) 600W 040215

FIGURE 8.  DIP SWITCH SETTINGS FOR USING RESET BUTTON OR REMOTE ON-OFF

3.6

PROTECTION CIRCUITS

The following protection features are implemented in the HSF (A, AM) 600W Series: overvoltage
and overtemperature (PAR. 3.6.1), overcurrent (PAR. 3.6.2), fan failure (PAR. 3.6.3), and under-
voltage (PAR. 3.6.4). The HSF (A, AM) 600W Series provides a configurable visual alarm (see
PAR. 3.7.1) as well as an option to use either relay contacts or logic levels for alarm signals (see
PAR. 3.7.2) 

3.6.1 OVERVOLTAGE AND OVERTEMPERATURE PROTECTION

When the output voltage of the HSF (A, AM) 600W Power Supply increases beyond the specified
values (see Table 2), at some point the output is cut OFF and the fan turns OFF. To restart (reset)
the unit, press and release the OUTPUT RESET switch on the front panel or, if the remote on/off
feature is in use (see PAR. 3.5), open connection between the ±RC pins and then reconnect the
pins. The unit may also be restarted by turning the POWER ON/OFF switch to OFF, waiting 40
seconds, then setting the POWER switch to ON.

When internal temperature of the HSF (A, AM) 600W Power Supply increases beyond the allow-
able limit, the output is cut OFF and the fans turn OFF. The restart cycle (Power ON) should not
begin until the temperature returns to within specifications. To restart (reset) the unit, set the
POWER ON/OFF switch to OFF, wait until unit cools, then set the POWER switch to ON. The
power supply cannot be reset using the remote ON-OFF feature unless the power supply remains
shut down for at least 40 seconds.

3.6.2 OVERCURRENT SETTING AND PROTECTION

The Overcurrent Protection (OCP) characteristic is constant current limiting, automatic recovery.
OCP operates when output current exceeds 105% (119% for 24V model) of maximum d-c output
current specification. The output automatically recovers when the overload condition is removed. 

CAUTION: Operating the unit under overcurrent or shorted conditions for more than 30

seconds may damage the unit. 

The OCP setting is fixed and is not user-adjustable.

3.6.3 FAN FAILURE

A cutoff of the fan supply voltage or a decrease in fan speed causes the output to shut down and the
fans to turn OFF. Fan failure and all the other protection circuit operations produce an alarm (see
PAR. 3.7.2). To restart (reset) the unit, press and release the OUTPUT RESET switch on the front
panel or, if the remote on/off feature is in use (see PAR. 3.5), open the connection between the
±RC pins and then reconnect the pins. The unit may also be restarted by turning the POWER ON/
OFF switch to OFF, waiting 40 seconds, then setting the POWER switch to ON. If fan rotation is
out of specification the power supply will not recover.

3043784

3

3  +RC

+RC  3

3

SW1

4

SW2

4

OFF

ON

OFF

ON

(FACTORY DEFAULT)

USE FRONT PANEL

RESET BUTTON

A

B

(LOGICAL LEVEL OR 

MECHANICAL SWITCH)

USE REMOTE ON-OFF

3

3

SW2

SW1

4

4

ON

OFF

OFF

ON

3  +RC

4  -RC & -PF

+RC  3

-RC & -PF  4

TAB

-RC & -PF  4

4  -RC & -PF

!

Содержание HSF 12-53A

Страница 1: ...el and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without...

Страница 2: ...g Latches 15 4 Load Connection 16 5 Connecting Multiple Power Supplies 16 1 HSF A AM Rear Panel Connector and RA 19 4C Rack Adapter I O Connector 1 2 Power Rating Vs Temperature 3 3 Mechanical Outline...

Страница 3: ...of 12V 15V 24V 28V or 48V They employ forward con version and power factor correction and are designed to operate in a fault tolerant power system Input voltage range is single phase 85 265V a c 47 63...

Страница 4: ...see PAR 3 7 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one voltage adjustment of a master power supply When REF...

Страница 5: ...requires that DIP SW1 position 7 be set to ON Refer to Table 5 for mini mum conditions required to maintain proper operation of alarm relay meter AM Models only and VDC ON ALARM indicator 2 Using tri...

Страница 6: ...0 2 Maximum 85 to 132V a c 170 to 265V a c Load Effect 0 6 Typical 1 Maximum default 0 6 Typical 1 Maximum see PAR 3 8 Individual Mode 0 100 load change Current Sharing 10 100 load change Temperature...

Страница 7: ...a c 50 60Hz ambient temperature 40 C max RoHS Compliance RoHS versions available contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B...

Страница 8: ...0 093 2 4 0 127 3 2 0 430 10 9 2 065 52 5 3 353 85 2 0 337 8 5 0 085 2 2 0 204 5 2 0 090 2 3 0 943 23 9 2 408 61 2 0 438 11 1 0 394 10 0 3 216 81 7 0 606 15 4 0 690 17 5 FRONT VIEW REAR VIEW SEE REAR...

Страница 9: ...6 CSB 1 OFF Enables Current Share always off ON N A 6 CSB 1 OFF N A ON Enables Current Share always on 7 COM to S OFF Isolates COM from S ON Connects COM to S 7 VADJ to 0 OFF Vadj adjusts output per T...

Страница 10: ...established at the factory The output voltage determines which key pins are installed see Figure 3 Detail A When the proper holes in the rack adapter are blocked by keying screws installed by the user...

Страница 11: ...ore unit is removed from the rack adapter Retaining Latches 2 Prevents inadvertent removal of unit from rack adapter see PAR 3 9 AM Models only Voltage Current meter Monitors out put voltage or curren...

Страница 12: ...pecified in Table 2 To ensure proper operation of the alarm relay meter AM Models only and VDC ON ALARM indicator do not adjust the external voltage below minimum listed in Table 5 Using External Resi...

Страница 13: ...other unlike earlier non A HSF 600W models This return is connected to the power supply OUTPUT Please contact Kepco if appli cation requires remote control to be isolated from DC output or from PF si...

Страница 14: ...wait until unit cools then set the POWER switch to ON The power supply cannot be reset using the remote ON OFF feature unless the power supply remains shut down for at least 40 seconds 3 6 2 OVERCURR...

Страница 15: ...N ALARM indicator can be disabled by setting DIP switch 1 position 8 to OFF 3 7 2 ALARM SIGNALS Either of two options are available for signalling alarms isolated relay contacts factory default PAR 3...

Страница 16: ...on the transistor cuts off and the collector emitter cir cuit is open Figure 12 is a timing diagram of the power fail signal The default state of the alarm is logic low The sink current for the optoco...

Страница 17: ...in conjunction with the RA 19 4C rack adapters to prevent unauthorized or inadvertent module extraction from an operating power system The latch is engaged by loosening the cap head screw approximatel...

Страница 18: ...e the difference between voltage settings of parallel con nected units should be less than 0 5 of the nominal voltage value of the units Output voltage adjustment should be done at same load for each...

Отзывы: