background image

HSF(A) 600W 040215

13

3.6.4 UNDERVOLTAGE

If power supply output voltage either falls within 40 to 80% of the rated output voltage value, or is
programmed below the minimum values listed in Table 5, an alarm occurs if the internal relay
alarm (factory default, see PAR. 3.7.2.1) is enabled. To restart (reset) the unit, press and release
the OUTPUT RESET switch on the front panel or, if the remote on/off feature is in use (see PAR.
3.5), open the connection between the ±RC pins and then reconnect the pins. The unit may also
be restarted by turning the POWER ON/OFF switch to OFF, waiting 40 seconds, then setting the
POWER switch to ON. To enable the alarm function when operating below the minimum values
listed in Table 5, refer to PAR. 3.7.2.2 to configure the optically-coupled alarm.

3.7

ALARM SETTINGS

3.7.1 VISUAL ALARM. 

When the unit is connected in a parallel configuration, the front panel VDC ON/ALARM indicator is
normally configured to light red if the respective power supply output voltage is lost or if the
POWER switch is set to OFF. This is enabled when DIP switch 1, position 8 is set to ON. This can
be useful to indicate the loss of output voltage from one parallel-connected power supply that may
not be readily apparent. For the visual alarm to function properly the minimums specified in Table 4
must be observed.

FIGURE 9.  DIP SWITCH SETTINGS FOR RED ALARM INDICATOR ENABLE/DISABLE

If desired, the red alarm indication of the VDC ON/ALARM indicator can be disabled by setting
DIP switch 1 position 8 to OFF.

3.7.2 ALARM SIGNALS. 

Either of two options are available for signalling alarms: isolated relay contacts (factory default,
PAR. 3.7.2.1) or logic level alarm signals ±PF (PAR. 3.7.2.2). The ±PF logic level alarm option
must be used if the power supply is intended to operate below the minimum voltages listed in
Table 5.

3.7.2.1 INTERNAL ISOLATED RELAY ALARM

The first option, the factory default setting, uses an isolated internal relay offering normally closed
(NC) and normally open (NO) contacts referenced to an isolated common (AL COM). These con-
tacts may be used to configure “close on failure” or “open on failure” alarm circuits. (Refer to the
Series RA 19-4C Manual for alarm configurations for multiple HSF (A, AM) power supplies.) Set-
ting position 5 of the DIP switches as shown in Figure 10A selects this option. The NC (pin 6 of the
rack adapter I/O connector) and NO (pin 7) signals are referenced to Alarm common (pin 14).

3.7.2.2 OPTICALLY-COUPLED LOGICAL ALARM

The second option uses optically-coupled logic level alarm signals, +PF (pin 5 of the rack adapter
I/O connector) and -PF (pin 13), provided directly from the internal power supply that is the heart
of the HSF (A, AM) power supply. The optically-coupled logic alarm is selected by setting position
5 of the DIP switches as shown in Figure 10B. This option functions even with output voltage
adjusted below the minimum voltages specified in Table 5. 

3043783

SW1

SW2

8

OFF

ON

OFF

ON

(FACTORY DEFAULT)

RED ALARM INDICATOR ENABLED

A

RED ALARM INDICATOR DISABLED

B

8

SW1

SW2

OFF

ON

ON

OFF

8 ALARM LED ENABLE

8 ALARM LED ENABLE

TAB

Содержание HSF 12-53A

Страница 1: ...el and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without...

Страница 2: ...g Latches 15 4 Load Connection 16 5 Connecting Multiple Power Supplies 16 1 HSF A AM Rear Panel Connector and RA 19 4C Rack Adapter I O Connector 1 2 Power Rating Vs Temperature 3 3 Mechanical Outline...

Страница 3: ...of 12V 15V 24V 28V or 48V They employ forward con version and power factor correction and are designed to operate in a fault tolerant power system Input voltage range is single phase 85 265V a c 47 63...

Страница 4: ...see PAR 3 7 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one voltage adjustment of a master power supply When REF...

Страница 5: ...requires that DIP SW1 position 7 be set to ON Refer to Table 5 for mini mum conditions required to maintain proper operation of alarm relay meter AM Models only and VDC ON ALARM indicator 2 Using tri...

Страница 6: ...0 2 Maximum 85 to 132V a c 170 to 265V a c Load Effect 0 6 Typical 1 Maximum default 0 6 Typical 1 Maximum see PAR 3 8 Individual Mode 0 100 load change Current Sharing 10 100 load change Temperature...

Страница 7: ...a c 50 60Hz ambient temperature 40 C max RoHS Compliance RoHS versions available contact Kepco Sales for further information EMC Emission Conducted Designed to meet FCC Class B VCCI Class B EN55011 B...

Страница 8: ...0 093 2 4 0 127 3 2 0 430 10 9 2 065 52 5 3 353 85 2 0 337 8 5 0 085 2 2 0 204 5 2 0 090 2 3 0 943 23 9 2 408 61 2 0 438 11 1 0 394 10 0 3 216 81 7 0 606 15 4 0 690 17 5 FRONT VIEW REAR VIEW SEE REAR...

Страница 9: ...6 CSB 1 OFF Enables Current Share always off ON N A 6 CSB 1 OFF N A ON Enables Current Share always on 7 COM to S OFF Isolates COM from S ON Connects COM to S 7 VADJ to 0 OFF Vadj adjusts output per T...

Страница 10: ...established at the factory The output voltage determines which key pins are installed see Figure 3 Detail A When the proper holes in the rack adapter are blocked by keying screws installed by the user...

Страница 11: ...ore unit is removed from the rack adapter Retaining Latches 2 Prevents inadvertent removal of unit from rack adapter see PAR 3 9 AM Models only Voltage Current meter Monitors out put voltage or curren...

Страница 12: ...pecified in Table 2 To ensure proper operation of the alarm relay meter AM Models only and VDC ON ALARM indicator do not adjust the external voltage below minimum listed in Table 5 Using External Resi...

Страница 13: ...other unlike earlier non A HSF 600W models This return is connected to the power supply OUTPUT Please contact Kepco if appli cation requires remote control to be isolated from DC output or from PF si...

Страница 14: ...wait until unit cools then set the POWER switch to ON The power supply cannot be reset using the remote ON OFF feature unless the power supply remains shut down for at least 40 seconds 3 6 2 OVERCURR...

Страница 15: ...N ALARM indicator can be disabled by setting DIP switch 1 position 8 to OFF 3 7 2 ALARM SIGNALS Either of two options are available for signalling alarms isolated relay contacts factory default PAR 3...

Страница 16: ...on the transistor cuts off and the collector emitter cir cuit is open Figure 12 is a timing diagram of the power fail signal The default state of the alarm is logic low The sink current for the optoco...

Страница 17: ...in conjunction with the RA 19 4C rack adapters to prevent unauthorized or inadvertent module extraction from an operating power system The latch is engaged by loosening the cap head screw approximatel...

Страница 18: ...e the difference between voltage settings of parallel con nected units should be less than 0 5 of the nominal voltage value of the units Output voltage adjustment should be done at same load for each...

Отзывы: