background image

6

HSF 300W 042315

Position 7 of SW1 either enables (default) or disables using the internal power supply
reference voltage to power the DC ON/ALARM indicator. Position 8 of SW2 either dis-
ables (default) or enables using the HSF output voltage to power the DC ON/ALARM
indicator (requires minimums per Table 4 if enabled) (see PAR 3.8).Only one of these
two must be enabled, the other disabled.

Position 8 of SW1 either disables (default) or enables the visual alarm indication (see
PAR. 3.7.1).

FIGURE 4.  DIP SWITCH CONFIGURATION

3.2

FRONT PANEL ACCESS. 

The front panel provides a power ON/OFF switch controlling input power and a "VDC ON" indica-
tor which lights green when the unit is operating. If the unit is connected in a parallel configuration,
the indicator lights red if the unit shuts off automatically, or the POWER switch is set to OFF. 

CAUTION: DO NOT repeatedly toggle the power ON/OFF switch as this may cause unit to

fault. 

NOTE: The ON/OFF switch must be set to OFF before removing unit from rack adapter. 

If remote on-off is not enabled (see PAR. 3.5), the OUTPUT RESET button restores output power
in the event that overcurrent or overvoltage protection has tripped, or thermal overload or fan mal-
function has occurred.

If remote voltage control (see PAR. 3.4.2) is not enabled, the front panel Vadj trimmer (see PAR.
3.4.1) provides adjustment of the output voltage within the limits specified in Table 2; test points
are available at the front panel for monitoring the DC output.

Figure 5 shows the location of all operating controls, indicators and test points followed by an
explanation of each. 

3.3

KEYING

Keying of the HSF 300W is established at the factory. The output voltage determines which key
pins are installed (see Figure 3, Detail A). When the proper holes in the rack adapter are blocked
by keying screws installed by the user, only a power supply of the correct voltage can be inserted
in the rack adapter slot. Refer to the RA 19-4C Manual for rack adapter keying instructions. 

OFF

ON

OFF

ON

ALARM LED DISABLE

DC ON PWR BY REF

-PF

+PF

-RC

+RC

RV

REF

3043278

8

8

8

SW1

SW2

4

6

7

5

2

3

1

4

4

5
6

7

6

7

5

1
2

3

2

3

1

DC ON PWR BY OUTP V

8

-RC

4

+PF

-COM

-PF

6

7

5

REF

+RC

RV

2

3

1

FACTORY DEFAULT SETTING:

 - FRONT PANEL VADJ CONTROL
 - RELAY ALARM SELECTED
 - VISUAL ALARM DISABLED
 - REMOTE ON-OFF DISABLED
 - DC ON PWR BY REF ENABLED

NOTE: NOT ALL COMPONENTS SHOWN.

DETAIL VIEW

SW1

SW2

SEE DETAIL VIEW

TAB

Содержание HSF 12-27

Страница 1: ...he correct revision for your particular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission...

Страница 2: ...Power Options 11 3 9 Local remote Sensing 12 3 10 Retaining Latches 12 4 Load Connection 12 5 Connecting Multiple Power Supplies 12 1 HSF Rear Panel Connector and RA 19 4C Rack Adapter I O Connector 1...

Страница 3: ...ack adapter accepts up to four 300W modules All input output connections are through a 24 pin connector that plugs in to the rack adapter All external connections described in the following paragraphs...

Страница 4: ...Amps 4 63 78 28 4 35 1 23 1 28 6 14 7 18 2 12 6 15 6 7 4 9 1 Short Circuit Current Amps 82 35 29 20 17 11 Overvoltage Protection OVP Volts d c 5 5 7 7 0 14 3 16 8 18 0 24 0 29 3 33 6 34 2 39 2 54 5 59...

Страница 5: ...nt flow into EMI filter 15A typ 20A max first surge 100 120V ac 30A typ 40 max first surge 200 240 V ac Leakage Current 0 24mA typ 0 3mA max 120V a c 60Hz per IEC 950 and UL1950 0 31mA typ 0 38mA max...

Страница 6: ...f 3 axes sweep time 10 minutes Shock Acceleration 643 5ft s2 196 1M s2 20g Pulse Duration 11ms 5 msec non operating 1 2 sine pulse three shocks on each axis Power Supply is fixed on its bottom side Sa...

Страница 7: ...front panel reset button to be used to reset the unit after a fault or allow Remote on off via mechanical switch or logic level see PAR 3 5 Positions 5 and 6 allows alarm signals to be produced from e...

Страница 8: ...er in the event that overcurrent or overvoltage protection has tripped or thermal overload or fan mal function has occurred If remote voltage control see PAR 3 4 2 is not enabled the front panel Vadj...

Страница 9: ...ONTROL Output voltage can be manually adjusted with the voltage adjustment control Vadj see Figure 5 for location when DIP switches SW1 and SW2 see Figure 4 for location are configured as shown in Fig...

Страница 10: ...the output may be turned ON or OFF using the RC signals if the remote ON OFF feature is enabled Note that when remote ON OFF is enabled the RESET OUTPUT switch does not function Remote ON OFF is enabl...

Страница 11: ...beyond allowable limit the output is cut OFF and the fans turn OFF The restart cycle Power ON should not begin until the temperature returns to within specifications To restart reset the unit set the...

Страница 12: ...imums per Table 4 if enabled see PAR 3 8 3 7 2 ALARM SIGNALS Either of two options are available for signalling alarms isolated relay contacts factory default PAR 3 7 2 1 or logic level alarm signals...

Страница 13: ...IRCUIT OPTICALLY ISOLATED FIGURE 11 PF POWER FAILURE OPTOCOUPLER TIMING DIAGRAM 3 8 VDC ON ALARM INDICATOR POWER OPTIONS To use the internal power supply reference voltage to power the VDC ON ALARM in...

Страница 14: ...POWER SUPPLIES All connections to multiple HSF power supplies must be made via the I O mating connectors at rear of the Rack Adapter or by the Rack Adapter DIP switches These connections including th...

Отзывы: