background image

12

HSF 300W 042315

3.9

LOCAL/REMOTE SENSING

HSF 300W Power Supplies allow remote error sensing which can compensate up to 0.4 Volts per
load wire. Local/Remote error sensing is configured by means of separate DIP switches mounted
on the RA 19-4C Rack Adapter (see RA 19-4C Rack Adapter Operator Manual). Either local or
remote sensing MUST be used, otherwise the units will not operate. 

3.10

RETAINING LATCHES

HSF 300W series power supplies are provided with (2) retention latches located at each side of
the bottom edge of the front panel (see Figure 5). These latches work in conjunction with the RA
19-4C rack adapters to prevent unauthorized or inadvertent module extraction from an operating
power system. The latch is engaged by loosening the cap-head screw approximately 1/2 turn
CCW (use 5/32” hex key) and sliding the latch down to the bottom of the slot, then retightening the
cap-head screw CW until snug. DO NOT OVERTIGHTEN! To release, follow the same procedure,
except lift the latch to the top of the slot. Be sure to move the latch completely up or down to
ensure full engagement and disengagement of the latching mechanism. When the HSF power
supply is not installed in its plug-in rack adapter, it is recommended that the latch be secured in
the open (up) position to prevent damage. 

NOTE: Retaining latches must 

not

 be used to secure the HSF power supply in the rack

adapter for shipping purposes.

4.

LOAD CONNECTION

Connect the load to (+) and (–) terminals at the rear panel of the Rack Adapter (see RA 19-4C
Instruction Manual for details).

5.

CONNECTING MULTIPLE POWER SUPPLIES

All connections to multiple HSF power supplies must be made via the I/O mating connectors at
rear of the Rack Adapter or by the Rack Adapter DIP switches. These connections, including the
configuration of the two internal HSF DIP switches, are described in the Rack Adapter Instruction
manual, and include:

Using one power supply to control the output of multiple supplies.

Using parallel master/slave configurations (for increased current or redundancy) where
the user either predetermines the master or allows the load to determine which is the
master. These configurations also cover the use of the Current Balancing feature of the
HSF power supply. 

Using series configurations (for increased voltage).

Using open-on-fail or close-on-fail alarm schemes with multiple power supplies.

 NOTE: If parallel-connected units are controlled individually, either a minimum load or voltage

set restrictions are required to avoid slave “idle” or slave “oscillating output” conditions
(When the slave is idle, the output is off, no lights are lit, and the alarm is set.) If the
minimum load is maintained, voltage set restrictions are not required. 

Minimum Load: 

The minimum load (Amperes) = N x (I/10) where N = the number of

units in parallel, I = Nominal current rating of individual power supply (Amperes). For
applications requiring no load or lower than minimum load conditions refer to the Volt-
age Set Restrictions specified below. Load effect specifications will not be met when
units are operated in redundant mode with load less than 10% per unit.

Voltage Set Restrictions: 

To avoid slave 

idle

 all parallel-connected units’ output

voltage must be set within 1% or 200mV of each other (whichever is lower) and be at
least 80% of their nominal (rated) output voltage (90% for 48V model).

Содержание HSF 12-27

Страница 1: ...he correct revision for your particular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission...

Страница 2: ...Power Options 11 3 9 Local remote Sensing 12 3 10 Retaining Latches 12 4 Load Connection 12 5 Connecting Multiple Power Supplies 12 1 HSF Rear Panel Connector and RA 19 4C Rack Adapter I O Connector 1...

Страница 3: ...ack adapter accepts up to four 300W modules All input output connections are through a 24 pin connector that plugs in to the rack adapter All external connections described in the following paragraphs...

Страница 4: ...Amps 4 63 78 28 4 35 1 23 1 28 6 14 7 18 2 12 6 15 6 7 4 9 1 Short Circuit Current Amps 82 35 29 20 17 11 Overvoltage Protection OVP Volts d c 5 5 7 7 0 14 3 16 8 18 0 24 0 29 3 33 6 34 2 39 2 54 5 59...

Страница 5: ...nt flow into EMI filter 15A typ 20A max first surge 100 120V ac 30A typ 40 max first surge 200 240 V ac Leakage Current 0 24mA typ 0 3mA max 120V a c 60Hz per IEC 950 and UL1950 0 31mA typ 0 38mA max...

Страница 6: ...f 3 axes sweep time 10 minutes Shock Acceleration 643 5ft s2 196 1M s2 20g Pulse Duration 11ms 5 msec non operating 1 2 sine pulse three shocks on each axis Power Supply is fixed on its bottom side Sa...

Страница 7: ...front panel reset button to be used to reset the unit after a fault or allow Remote on off via mechanical switch or logic level see PAR 3 5 Positions 5 and 6 allows alarm signals to be produced from e...

Страница 8: ...er in the event that overcurrent or overvoltage protection has tripped or thermal overload or fan mal function has occurred If remote voltage control see PAR 3 4 2 is not enabled the front panel Vadj...

Страница 9: ...ONTROL Output voltage can be manually adjusted with the voltage adjustment control Vadj see Figure 5 for location when DIP switches SW1 and SW2 see Figure 4 for location are configured as shown in Fig...

Страница 10: ...the output may be turned ON or OFF using the RC signals if the remote ON OFF feature is enabled Note that when remote ON OFF is enabled the RESET OUTPUT switch does not function Remote ON OFF is enabl...

Страница 11: ...beyond allowable limit the output is cut OFF and the fans turn OFF The restart cycle Power ON should not begin until the temperature returns to within specifications To restart reset the unit set the...

Страница 12: ...imums per Table 4 if enabled see PAR 3 8 3 7 2 ALARM SIGNALS Either of two options are available for signalling alarms isolated relay contacts factory default PAR 3 7 2 1 or logic level alarm signals...

Страница 13: ...IRCUIT OPTICALLY ISOLATED FIGURE 11 PF POWER FAILURE OPTOCOUPLER TIMING DIAGRAM 3 8 VDC ON ALARM INDICATOR POWER OPTIONS To use the internal power supply reference voltage to power the VDC ON ALARM in...

Страница 14: ...POWER SUPPLIES All connections to multiple HSF power supplies must be made via the I O mating connectors at rear of the Rack Adapter or by the Rack Adapter DIP switches These connections including th...

Отзывы: