background image

©2006, KEPCO, INC

1

Data subject to change without notice

228-1301 REV 4

I N S T R U C T I O N   M A N U A L

KEPCO

KEPCO, INC. 

 " 

 131-38 SANFORD AVENUE 

 "

  FLUSHING, NY. 11352 U.S.A.

  "

  TEL (718) 461-7000

  " 

 FAX (718) 767-1102

  

http://www.kepcopower.com   

 email: [email protected]

An ISO 9001 Company.

HSF

150W

KEPCO SINGLE OUTPUT 150 WATT 

HOT SWAP PLUG-IN POWER SUPPLIES

I — INTRODUCTION

The Kepco HSF 150 Watt Series hot swappable, high frequency switching, plug-in power supplies employ forward conversion

and are designed to operate in a fault tolerant power system with either a-c or d-c input. A resistor and thyristor soft-start circuit

limits start-up surge. A built-in forced current share circuit and OR-ing diodes allow configuration for hot-swap and parallel-

redundant N+1 operation. 

These power supplies are designed to be used with Kepco’s Series RA 19-(X)B rack adapters (Figure 1). The RA 19-8B rack

adapter accepts up to eight 50 Watt or 100 Watt units; RA 19-7B accepts up to four 50 Watt or 100 Watt units and three 150 Watt

units;  RA 19-6B accepts up to six 150 Watt units (see Figure 1). All input/output connections are through a 24 pin connector that

plugs in to the rack adapter. All external connections are made through the rack adapter. Surface mount technology permits effi-

cient component layout for minimum mounting space. 

Six models may be selected for outputs of 5, 12, 15, 24, 28, or 48V (see Table 1).

When the input is cut off, the output is maintained for 15 milliseconds minimum. If the power supply shuts down due to an output

overvoltage condition, it is then necessary to wait 90 seconds minimum (120V a-c input) or 120 seconds minimum (240V a-c

input) before turning the unit on again. EMI filtering is designed to meet FCC Class B rating and VDE 0871 Class B rating. This

page contains specifications for each model of the HSF 150 Watt Series. Environmental specifications for each model are the

same.

II — FEATURES

FRONT PANEL ACCESS.  

The front panel provides a power ON/OFF switch controlling input power and a “VDC ON” light

which indicates when the unit is operating. 

NOTE: The ON/OFF switch must be set to OFF before removing unit from rack

adapter.

 The front panel “MASTER ON” LED lights when 1) the unit operates independently, or 2) the unit is used in parallel

redundant configurations while a) the output is less than 10% of nominal or b) the output is within 10% to 100% of nominal and

the unit is functioning as a master. In parallel redundant configurations, the module with the highest voltage functions as the

master. The other units are slaves, and track the output voltage of the master. Refer to 

Current Share Bus (CSB)

 on page 3 for

details. The front panel Vadj trimmer provides adjustment of the output voltage within the limits specified in Table 1; test points

connected to the +S and –S lines are available at the front panel for measuring the output. 

FORCED CURRENT SHARE CIRCUIT.  

When units are configured for N+1 parallel redundant operation, it is desirable for cur-

rent to be divided equally among the paralleled supplies. When the CSB (Current Share Bus) lines of paralleled HSF units are

connected together, the load current is forced to divide equally between all paralleled units. If one unit fails, the remaining units

will continue to supply the load, and the load current will be divided equally among the remaining operating units. The failed unit

is automatically isolated from the circuit by a built-in isolation diode. Refer to 

Current Share Bus (CSB)

 on page 3 for details.

TABLE 1.   OUTPUT RATINGS AND SPECIFICATIONS, HSF 150W SERIES

MODEL

HSF 5-30

HSF 12-12

HSF 15-10

HSF 24-6

HSF28-5

HSF 48-2.8

OUTPUT VOLTS, d-c (NOMINAL)

5V

12V

15V

24V

28V

48V

ADJUSTMENT RANGE

4.5 - 5.5V

11.4  - 12.6V

13.5 - 16.5V

22.5 - 25.5V

26.5 - 29.5V

45.0 - 51.0

OUTPUT CURRENT (NOMINAL)

(1)

(1) Derates same as Ouptut Power.

30A

12A

10A

6A

5A

2.8A

OUTPUT POWER (NOMINAL)

(2)

(2) See power derating curve, Figure 3.

150W

144W

150W

144W

140W

134.4W

RIPPLE

AND

NOISE

(mV p-p)

0-40°C

10-100% LOAD

source  (typ)

10

15

15

15

20

20

source (max)

20

30

40

40

40

40

switching  (typ)

30

35

40

50

60

80

switching (max)

60

70

80

110

140

220

spike noise (d-c—50MHz)

<120

<190

<220

<310

<330

<530

OVERVOLTAGE SETTING (25 °C, NOM. INPUT)

6.5 - 7.5V

13.7 - 15.7V

17.0 - 19.0V

27.0 - 30.5V

32.0 - 35.0

53.5 - 60.0

OVERCURRENT SETTING (25 °C, NOM. INPUT)

Rectangular type characteristic

32.0 - 36.0A

13.0 - 15.0A

11.0 - 13.0A

6.3 - 7.5A

5.3 - 6.1A

3.0 - 3.5A

Содержание HSF 12-12

Страница 1: ... OFF switch must be set to OFF before removing unit from rack adapter The front panel MASTER ON LED lights when 1 the unit operates independently or 2 the unit is used in parallel redundant configurations while a the output is less than 10 of nominal or b the output is within 10 to 100 of nominal and the unit is functioning as a master In parallel redundant configurations the module with the highe...

Страница 2: ...it Current nominal output at rated load 120V a c rms 3 0A a c typ 3 5A a c max 240V a c rms 1 5A a c typ 2 0A a c max Initial Turn on Surge one half of first input cycle 120V a c rms 25A max 240V a c rms 50A max When the a c input power is removed the inrush current limit circuit requires 30 seconds recovery time before the a c input power is reconnected Brownout Voltage 85V a c 110V d c Switching...

Страница 3: ...t to the load goes below 10 for each unit in current share mode all MASTER ON lights may go on see load effect specifications this indicates that forced cur rent share is no longer working units are simply in current share mode If forced current sharing at less than 10 nominal current per supply is needed contact Kepco application engineering Remote sensing is recommended For master slave operatio...

Страница 4: ...z 10 mm amplitude 10 55 Hz 2g acceleration SHOCK non operating one half sinusoidal pulse three shocks to each axis Acceleration 20g Duration 11ms 5ms OPERATING TEMPERATURE See Figure 4 STORAGE TEMPERATURE 40o C to 75o C OPERATING AND STORAGE RELATIVE HUMIDITY up to 95 wet bulb temp 35o C non condensing FUSE Quick acting 6 3A 250V 5 2 x 20mm San O P N EQ6 3A Kepco P N 541 0113 DIMENSIONS See Figure...

Отзывы: