SUPERtrol II Flow Computer
57
ll scale value for the high range transmitter analog input signal.
The value entered here must be identical to the value set for the
flowmeter.
Note:
• The units for differential pressure flowmeters are dependent
on the system units selected for pressure:
- Imperial units [inches H2O]
- Metric units: [mbar]
Input:
Number with floating decimal point: 0.000...999999
Display:
10000.00 ft3/h
FULL SCALE VALUE
Enter the value of delta P at which the unit will begin using the hi
range delta P pressure transmitter signal.
Input:
Number with floating decimal point: 0.000...999999
Display:
0.000 in H2O
SWITCH UP DP
Enter the value of delta P at which the unit will begin using the lo
range delta P pressure transmitter signal.
Input:
Number with floating decimal point: 0.000...999999
Display:
0.000 in H2O
SWITCH UP DP
Enter the low flow cutoff. This is used as a switchpoint for creep
suppression. This can be used to prevent low flows from being
registered.
Input:
Number with floating decimal point: 0.000...999999
Display:
.000 ft3/h
LOW FLOW CUTOFF
6.8
FLOW INPUT
(Continued)
FLOW INPUT
FULL SCALE-HI
RANGE
SWITCH UP DP
SWITCH DOWN DP
LOW FLOW
CUTOFF