SUPERtrol II Flow Computer
40
DISPLAY
6.5
DISPLAY
Select the variable that are to be displayed in the "HOME position"
during normal operation. Each variable can be assigned to line 1
(L1), line 2 (L2) or NO (removed from scroll list).
Note:
• To initiate the scroll list press the SCROLL key. The list will
be displayed in groups of two, each group is displayed for
approximately 3 to 4 seconds.
• Any alarm messages will be displayed periodically,
alternating throughout the scroll list.
Selection (with Prompt):
CHANGE? YES, NO
ADD TO LIST? L1, L2, NO
Variable Selection:
HEAT FLOW, MASS FLOW, VOLUME FLOW, STD.
VOLUME FLOW, TEMP.1, TEMP.2, DELTA T, PRESSURE,
DENSITY, SPEC. ENTHALPY, TIME, DATE, HEAT TOTAL,
HEAT GRAND TOTAL, MASS TOTAL, MASS GRAND
TOTAL, STD VOLUME TOTAL, STD.V. GRAND TOTAL,
VOLUME TOTAL, VOL. GRAND TOTAL, PEAK DEMAND,
DEMAND LAST HOUR, PEAK DEMAND TIME, PEAK
DEMAND DATE
Note:
Variable selection will vary depending on Flow Equation
selected and options supplied.
Display:
ADD TO LIST? L1
HEAT FLOW?
SCROLL LIST
The "display damping" constant is used to stabilize fluctuating
displays. The higher the constant, the less fluctuation will be
displayed.
Note:
Relay response time is affected by the value entered for
display damping. The larger the display damping value,
the slower the relay response time will be. This is intended
to prevent false triggering of the relays. Enter a display
damping factor of zero (0) for fastest response time.
Note:
• Factory setting: 1
Input:
2 digits max; 0...99
Display:
CONSTANT? 1
DISPLAY DAMPING
DISPLAY
DAMPING