SUPERtrol II Flow Computer
55
6.8
FLOW INPUT
(Continued)
FLOW INPUT
Select the type of square law flowmeter to be used with the
instrument.
Note:
This selection will only appear if one of the Square Law
selections were made in "FLOWMETER TYPE".
Selection:
ORIFICE, V-CONE, ANNUBAR, PITOT, VENTURI, FLOW
NOZZLE, BASIC SQRLAW/TARGET, WEDGE, VERABAR,
ACCELABAR
Display:
ORIFICE
SQUARE LAW FLOWMETER
Select the size of the ILVA flowmeter.
Selection:
DN50, DN80, DN100, DN150, DN200, DN250, DN300
Select the size of the Accelabar flowmeter.
Selection:
1 inch, 2 inch, 3 inch, 4 inch, 6 inch, 8 inch, 10 inch, 12 inch
Select the type of measuring signal produced by the flowmeter.
Selection:
DIGITAL, 10 mV LEVEL
Voltage pulses, 10mV
trigger threshold.
DIGITAL, 100 mV LEVEL
Voltage pulses, 100mV
trigger threshold.
DIGITAL, 2.5 V LEVEL
Voltage pulses, 2.5V trigger
threshold.
4-20 mA
4-20 mA current signal
0-20 mA
0-20 mA current signal
4-20 mA STACKED
4-20 mA current signal
0-20 mA STACKED
0-20 mA current signal
0-5 V
0-5 V voltage signal
1-5 V
1-5 V voltage signal
0-10 V
0-10 V voltage signal
Display:
4-20 mA
INPUT SIGNAL
SQUARE LAW
FLOWMETER
ILVA METER SIZE
ACCELABAR SIZE
INPUT SIGNAL