1
SECTION 1 INTRODUCTION
1-1 General Description
1-1 General Description
Sections 1 through 8 of this manual describe
the wiring, programming and functionality of
the standard Batch controller. Section 9 de-
scribes the wiring, programming and function-
ality of Batch controllers with software version
8.7 (Option 6). Software version 8.7 incor-
porates Remote Start, Stop & Reset with EZ
PRE (easy preset). EZ PRE is a useful tool
for applications that require frequent changes
to the Preset amount.
The Batch controller uses the following soft-
ware versions:
VER 8.7 (Basic unit; Remote Start, Stop
& Reset with EZ PRE “Easy
Preset”)
VER 12.0 (Option 4; 16 point linearization)
1-2 Typical Application
1-2 Typical Application
The above application involves liquid fl ow.
The start button is pushed and the Batcher
receives pulses from the fl owmeter. The puls-
es are scaled by the K Factor and sent out via
the pulsed output to an external counter. The
Analog output is directed to a strip chart re-
corder which gives a hardcopy of the rate. As
the Prewarn is reached, the control valve par-
tially closes. When the fi nal Preset is reached
the valve shuts down completely. At any time
the fl ow can be suspended by hitting the stop
button. Through the serial communications, a
computer keeps a record of the daily events.
1 2 3 4 5 6
Flowmeter
Computer
Solenoid Valve
Solenoid V
Solenoid V
Remote
Totalizer
T
T
Strip Chart
Recorder
Pulse Output
RS232
Output
Analog
Output
1-3 Principles of Operation
1-3 Principles of Operation
Presets
When the start button is pushed, two relays
engage simultaneously to start fl ow. When
the prewarn number is reached, one re-
lay drops out. When the preset number is
reached, the other relay drops out. The user
may enter the two numbers when setting up
the batch counter. The prewarn is set a cer-
tain number of counts less than the preset
number. If the prewarn is set larger than the
preset, the message “PREWRONG” will ap-
pear on the display.
Ratemeter
Accurate to 5 1/2 digits (±1 display digit).
The ratemeter can be programmed to ac-
cept almost any number of pulses per unit of
measurement, sample from 2 to 24 seconds
maximum, and auto range up to 6 digits of
signifi cant information. The ratemeter with a
K Factor of 1 displays the rate of pulses per
second. Simply dial in the proper K Factor
to display in minutes, hours or other units of
measurement. Press the C button, while the
unit is displaying the batch, to display the rate;
‘R’ is displayed on the left side of the display.
K Factor
The K Factor is used to convert the input puls-
es or analog input into workable units. The
8 digit K Factor is a divider with a range of
0.00011 to 99999999 (the decimal point may
be keyed into any position). Separate K Fac-
tors may be entered into the count and rate
sections of the Batcher. Thus, you may batch
in gallons and display rate in liters per hour.
The maximum factored count speed is 20000
Hz. The maximum factored rate is 7 digits.
16 Point Linearization
(Optional)
This option extends the accurate range by al-
lowing users to dial in different K Factors for
different input rates. This option may be used
with digital or analog inputs. (See Section 7-
3.)