24. Record of Configuration 

Use  the  table  below to  record  the configuration codes  that have been  set on the  control  panel  for  future 
reference. Place a tick in the grey band for any configuration options that are set. 

It is recommended that a copy of this table is left with the control panel under the supervision of the person 

responsible for the fire detection system. 

 

 

CODE  

FUNCTION 

COMMENTS 

SET 

00 

SOUNDER DELAY TIME = 30 SECONDS 

Sets the time delay before sounders operate in combination with 
configuration codes 31 to 48 and access level 2 function AD. 
 

 

01 

SOUNDER DELAY TIME = 1 MINUTE 

 

02 

SOUNDER DELAY TIME = 2 MINUTES 

 

03 

SOUNDER DELAY TIME = 3 MINUTES 

 

04 

SOUNDER DELAY TIME = 4 MINUTES 

 

05 

SOUNDER DELAY TIME = 5 MINUTES 

 

06 

SOUNDER DELAY TIME = 6 MINUTES 

 

07 

SOUNDER DELAY TIME = 7 MINUTES 

 

08 

SOUNDER DELAY TIME = 8 MINUTES 

 

09 

SOUNDER DELAY TIME = 9 MINUTES 

 

10 

COMMON ALARM MODE 

All sounders operate upon any fire condition 

 

11 

TWO-STAGE ALARM MODE 

Continuous sounders in activated zone, pulsing elsewhere 

 

12 

ZONED ALARM MODE 

Only sounders connected to zone in alarm operate 

 

 21* 

DISABLE FIRE BUZZER 

Buzzer will not operate on fire condition 

 

 22* 

DISABLE FAULT OUTPUT 

Fault relay will not operate except upon total power failure 

 

23 

DISABLE EARTH FAULT MONITORING 

Connection of fire alarm wiring will not announce a fault  

 

24 

PULSED REMOTE CONTROL OUTPUT 

Aux 24V supply pulses 1 sec on/1 sec off 

 

25 

ENABLE SOUNDERS ON DETECTION CIRCUITS 

Set as default if panel is two wire “T” series (detectors and call 
points on same cables) 

 

26 

DISABLE FIRE OUTPUT 

Fire relay will not operate upon any alarm 

 

27 

REMOVE AUX 24 UPON PANEL RESET 

24V supply switches off for about 5 seconds when panel is reset 

 

28 

INDICATE CALL POINT ACTIVATION 

Activation of a call point with a 270R resistance fitted is indicated 
by a flashing zone indicator and “Pu” on the 7 segment display. 
Activation  of  a  detector  will  be  indicated  by  a  steady  zone 
indicator and nothing on the 7 segment display 

 

29 

DO  NOT  RE-SOUND  ALARMS  FROM  ANOTHER 
ZONE 

Silenced sounders will not re-sound upon further zone activations 

 

2A 

TREAT CALL POINT ALARM AS DETECTOR ALARM 

When  this  option  is  active,  the  panel  does  not  distinguish 
between detector alarms and call point alarms (v215 onward) 

 

31 

ZONE 1 ALARM FROM DETECTOR DELAYED 

Sounder outputs will be delayed by time set at options 
0-9 when selected zone(s) triggered by detector only. 
Note  access  level  2  function  Ad  must  be  set  for  this  to  take 
effect. 

 

32 

ZONE 2 ALARM FROM DETECTOR DELAYED

 

 

33 

ZONE 3 ALARM FROM DETECTOR DELAYED

 

 

34 

ZONE 4 ALARM FROM DETECTOR DELAYED

 

 

35 

ZONE 5 ALARM FROM DETECTOR DELAYED

 

 

36 

ZONE 6 ALARM FROM DETECTOR DELAYED

 

 

37 

ZONE 7 ALARM FROM DETECTOR DELAYED

 

 

38 

ZONE 8 ALARM FROM DETECTOR DELAYED

 

 

41 

ZONE 1 ALARM FROM CALL POINT DELAYED 

Sounder outputs will be delayed by time set at options 
0-9 when selected zone(s) triggered by call point only. 
Note  access  level  2  function  Ad  must  be  set  for  this  to  take 
effect. 

 

42 

ZONE 2 ALARM FROM CALL POINT DELAYED

 

 

43 

ZONE 3 ALARM FROM CALL POINT DELAYED

 

 

44 

ZONE 4 ALARM FROM CALL POINT DELAYED

 

 

45 

ZONE 5 ALARM FROM CALL POINT DELAYED

 

 

46 

ZONE 6 ALARM FROM CALL POINT DELAYED

 

 

47 

ZONE 7 ALARM FROM CALL POINT DELAYED

 

 

48 

ZONE 8 ALARM FROM CALL POINT DELAYED

 

 

51 

COINCIDENCE ZONE 1 

Zone contributes to ancillary board coincidence O/P. Any number 
of zones can be selected to contribute. 

 

52 

COINCIDENCE ZONE 2 

 

53 

COINCIDENCE ZONE 3 

 

54 

COINCIDENCE ZONE 4 

 

55 

COINCIDENCE ZONE 5 

 

56 

COINCIDENCE ZONE 6 

 

57 

COINCIDENCE ZONE 7 

 

58 

COINCIDENCE ZONE 8 

 

61 

CONFIGURE Z1 FOR I.S BARRIER 

Detection threshold changed for use with IS barrier 

 

62 

CONFIGURE Z2 FOR I.S BARRIER 

 

63 

CONFIGURE Z3 FOR I.S BARRIER 

 

64 

CONFIGURE Z4 FOR I.S BARRIER 

 

65 

CONFIGURE Z5 FOR I.S BARRIER 

 

66 

CONFIGURE Z6 FOR I.S BARRIER 

 

67 

CONFIGURE Z7 FOR I.S BARRIER 

 

68 

CONFIGURE Z8 FOR I.S BARRIER 

 

 

 

 

 

Содержание Sigma CP K Series

Страница 1: ......

Страница 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Страница 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Страница 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Страница 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Страница 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Страница 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Страница 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Страница 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Страница 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Страница 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Страница 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Страница 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Страница 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Страница 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Страница 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Страница 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Страница 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Страница 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Страница 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Страница 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Страница 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Страница 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Страница 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...