background image

Man-1078_Sigma_CP_22 
 

     Page 21 of 24

 

21. Power supply 

The control panel requires a 230V (+10%/-15%), 50/60Hz, AC mains power supply which connects to the 
fused terminal block labelled “230V”. 

The fused terminal block contains a 20mm, F1.6A L250V fuse which should only be replaced with a similar 

type. 

The output voltage of the power supply is 28V DC +/- 2V and the total current rating including a maximum 

0.7A for battery charging is 3 Amps. Fuse F12 mounted on the circuit board is a self-resetting electronic fuse 

rated at 4 Amps. 
The incoming mains cable should be routed well away from other lower voltage wiring by a distance of at 

least 50mm. 

Mains wiring should include an earth conductor which is securely bonded to the building earth and should 

enter the enclosure as close as possible to the mains terminal block. Mains wires should be kept very short 

inside the enclosure and secured together close to the mains terminal block with a cable tie. 

The control panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity (see 
table 2 for battery size required for each model). 

The maximum current drawn from the batteries when the main power source is disconnected is 3 Amps. 

Battery leads are supplied wired to the PCB along with a link to connect the two batteries in series. The PCB 

is fitted with a 20mm, 3.15A T1 glass fuse (F13) in the battery charging circuit which must only be replaced 

with one of the same type. 
It is most important that the polarity of the batteries is carefully observed when connecting.  

 

When  the  batteries  are  discharged  to  a  level  at  which  a  low  battery  indication  is  given,  the  BATT  FAIL 

indicator will also be lit. 

 

Wrongly connected batteries could cause damage to the control panel. 

 

Caution: RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. 
DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS.

 

 

Figure 9 – Mains and battery connections 

 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1B 

N

N

L

L

E

+

-

+

-

GREY LINK

BLACK BATTERY 
LEAD TO  - 

TERMINAL

RED BATTERY 
LEAD TO + 

TERMINAL

MAINS 

TERMINAL

KEEP MAINS WIRES AS SHORT AS POSSIBLE 

AND SECURE ALL THREE WIRES CLOSE TO 

THE TERMINAL BLOCK WITH A CABLE TIE

Содержание Sigma CP K Series

Страница 1: ......

Страница 2: ...contacts 13 12B13 Connection to Repeater panels 13 13B14 Connection to Ancillary boards 14 14B15 Connection to 8 way Sounder boards 14 15B16 Panel operation 15 16B17 Configuration options 16 17B18 Wa...

Страница 3: ...operate upon fire condition These are to be used for local control and signalling 1B2 Safety and mounting Suppliers of articles for use at work are required under section 6 of the Health and Safety a...

Страница 4: ...t with electronic fuse Dedicated sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp total load over UallU circuits Zonal sounder outputs 24V Fused at 500mA with electronic fuse 1 6 Amp to...

Страница 5: ...IONISATION Apollo 32 55000 217 SERIES 65 IONISATION Apollo 32 55000 218 SERIES 65 IONISATION Apollo 32 55000 219 SERIES 65 IONISATION Apollo 32 55000 220 SERIES 65 IONISATION Apollo 32 55000 315 SERI...

Страница 6: ...connected to a zone this number should be limited to 32 to ensure that a short or open circuit on the wiring does not prevent the indication of a fire alarm from more than 32 fire detectors and or cal...

Страница 7: ...470R KC For standard 4 wire systems CX 470 OHM CALL POINT Fulleon NCP T CALL POINT Nittan ELECTRONICS FREE BASES ALL Note LCMU Line Continuity Monitoring Device part number K1406 allows call points mo...

Страница 8: ...system diagram which should be supplied by the detector manufacturer The power rating of the end of line resistor will be dependent upon the Zone classification rating Gas class this will be specified...

Страница 9: ...the three way terminal block on the left hand side of the PCB The fascia of the control panel is held in place by countersunk screws Undo the two screws and lift the fascia gently away from the box t...

Страница 10: ...ntrol panels from time to time and when this is done the operating software of the unit is updated The software revision can be located on the main processor by removing the plate holding the PCB from...

Страница 11: ...pplied fitted to the control panels terminals and placing them across the last device that is wired to the zone circuit Detection zone circuits must be wired as a single radial circuit with no spurs o...

Страница 12: ...n any one circuit 9B10 Connection to remote control terminals Some functions of the control panel can be controlled externally from the panel if required Operation of these inputs must be restricted b...

Страница 13: ...of a fire condition on any of the zones or pressing of the sound alarm button on the front panel The relay will remain activated until the alarm is silenced or the panel is reset This relay will not o...

Страница 14: ...s containing boards labelled S4XXA or above They will not work with panels containing boards without an alpha suffix 14B15 Connection to 8 way Sounder boards Sounder boards connect via a 2 core cable...

Страница 15: ...to light indicating a fault on the wiring to the sounder circuits 30B16 7 Power fault Failure of the mains power disconnection of the standby battery or high impedance in the charging circuit will cau...

Страница 16: ...mber appears Pressing the Enter button will cause the Test and Zone Fault LEDs to illuminate indicating the zones which are in test mode Disablements and zone tests are cleared by repeating the sequen...

Страница 17: ...r will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM ANOTHER ZONE Silenced sounders will not re sound upon further zone activations 2A TRE...

Страница 18: ...NOT SOUND ALARMS 94 ZONE 4 DOES NOT SOUND ALARMS 95 ZONE 5 DOES NOT SOUND ALARMS 96 ZONE 6 DOES NOT SOUND ALARMS 97 ZONE 7 DOES NOT SOUND ALARMS 98 ZONE 8 DOES NOT SOUND ALARMS A1 ZONE 1 ANY ALARM DEL...

Страница 19: ...the control panel a number of internal indicators are visible with the front cover removed as follows 39B20 1 Mains fail Indicates that the 230V AC supply is not present and the system is running on s...

Страница 20: ...ime until over rated circuit trips fuse to identify troublesome circuit 46B20 8 S1 fault and S2 fault Indicates a short or open circuit on sounder outputs Remove wiring and refit end of line resistors...

Страница 21: ...panel can accept sealed lead acid rechargeable batteries of up to 7Ah maximum capacity see table 2 for battery size required for each model The maximum current drawn from the batteries when the main...

Страница 22: ...ire alarm system in accordance with BS5839 Part 1 2002 will identify any malfunction of the control panel and any malfunction should be reported to the fire alarm maintenance company immediately Shoul...

Страница 23: ...by a flashing zone indicator and Pu on the 7 segment display Activation of a detector will be indicated by a steady zone indicator and nothing on the 7 segment display 29 DO NOT RE SOUND ALARMS FROM...

Страница 24: ...DOES NOT SOUND ALARMS 99 A1 ZONE 1 ANY ALARM DELAYED Zone needs to be triggered for 30 seconds continuously before an alarm is generated A2 ZONE 2 ANY ALARM DELAYED A3 ZONE 3 ANY ALARM DELAYED A4 ZON...

Отзывы: