AO4 U/I
– 12-Bit
Kendrion Kuhnke Automation GmbH
74
Error Log 2003
h
Name
Error Log
Index
2003
h
Object Code
RECORD
No. of Elements
9
Data Type
UNSIGNED32
Name
Number of errors
Subindex
00
h
Data type
UNSIGNED8
Access
read write
PDO Mapping
No
Default Value
00h
Name
Standard error field
Subindex
01
h
.. 08
h
Data type
UNSIGNED32
Access
read only
PDO Mapping
No
Default Value
00000000h
If a new error occurs, it is written to subindex 1. The existing entries in subindexes 1 to 7 are moved one
position backwards. The error on subindex 7 is removed.
The number of errors that have already occurred can be read from the object with the subindex 0. If a "0" is
written in this object, the counting starts again.
The object contains the error numbers from the object Error Code 213F
Sample Count 2100
h
Name
Sample Count
Index
2100
h
Object Code
VARIABLE
No. of Elements
0
Data Type
UNSIGNED32
Access
read only
PDO Mapping
Yes, TX-PDO
Value Range
Default Value
00
h
Number of samples since reset / restart