Kendrion Kuhnke Automation GmbH
AI 4-I
143
Options
You can set up the following options for every channel:
Name
Value
Explanation
InputProperties
0
Off (default)
5
4-20mA
6
0-20mA
Average
n=1..255
Inputn= average after n cycles (default=1)
StateWord
The state word (DWORD) is indicative of the module state:
Bit
Name
Explanation
0
ResetErrorAck
Acknowledges "Reset Error" in Module Control
1
Undervoltage24
Power to passive sensors < 19 V (no error, just info)
2
EtherCATError
Sync Manager Watchdog
3
ConfigError
Mismatch of Sync Manager's quantity structure
4-7
not used
8
Input0low
Current at 4-20mA < 3.5mA
9
Input1low
Current at 4-20mA < 3.5mA
10
Input2low
Current at 4-20mA < 3.5mA
11
Input3low
Current at 4-20mA < 3.5mA
12-15
not used
16
Input0high
Current > 20.5 mA
17
Input1high
Current > 20.5 mA
18
Input2high
Current > 20.5 mA
19
Input3high
Current > 20.5 mA
20-31
-
not used
Analogue Inputs
Check the following variables for the digitised input values:
Variable
Data type Explanation
Inputn
INT
Value of channel n (n=0…3).
ControlWord
The control word contains a bit for acknowledging errors.
Bit
Name
Explanation
0
ResetError
0 -> errors are retained, 1 -> errors cleared after removing their cause
1-15
-
not used
Object Dictionary
Index
Name
Type
Default
Min Max
Access
1000
Device Type
UINT32
0x40191
RO
1001
Error Register
UINT8
RO
1008
Device Name
String
AI4-I 12-Bit
RO
1009
Hardware Version
String
1.00
RO
100A
Software Version
String
1.00
RO
1018
Identity Object
Array
1018, 0
Number of Entries
UINT8
4
RO
1018, 1
Vendor Id
UINT32
0x0048554B
RO
Содержание Kuhnke FIO AI4
Страница 1: ...Instruction Manual Kuhnke FIO analogue IO Modules IP20 EtherCAT I O Modules E 747GB V2 28 01 2020...
Страница 36: ...AO4 U I 12 Bit Kendrion Kuhnke Automation GmbH 36 E 747GB V2 28 January 2020...
Страница 71: ...Kendrion Kuhnke Automation GmbH AI4 12Bit AO4 16Bit E 747GB V2 71 28 January 2020...
Страница 103: ...Kendrion Kuhnke Automation GmbH AI4 12Bit AO4 16Bit E 747GB V2 103 28 January 2020...