![Kendrion Kuhnke FIO AI4 Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/kendrion/kuhnke-fio-ai4/kuhnke-fio-ai4_instruction-manual_663790080.webp)
AO4 U/I
– 12-Bit
Kendrion Kuhnke Automation GmbH
80
Error Code 213F
h
Name
Error Code
Index
213F
h
Object Code
VARIABLE
No. of Elements
0
Data Type
UNSIGNED16
Access
read only
PDO Mapping
Yes, TX-PDO
Value Range
Default Value
00
h
2320
h
AO0 Temperature to high
2321
h
AO1 Temperature to high
2322
h
AO2 Temperature to high
2323
h
AO3 Temperature to high
2330
h
AI0 Overvoltage or wire break
2331
h
AI1 Overvoltage or wire break
2332
h
AI2 Overvoltage or wire break
2333
h
AI3 Overvoltage or wire break
3120
h
Module undervoltage
5100
h
AI0 Input value outside the parameterized limits
5101
h
AI1 Input value outside the parameterized limits
5102
h
AI2 Input value outside the parameterized limits
5103
h
AI3 Input value outside the parameterized limits
5300
h
AI0 sensor fault (Current less than 4mA)
5301
h
AI1 sensor fault (Current less than 4mA)
5302
h
AI2 sensor fault (Current less than 4mA)
5303
h
AI3 sensor fault (Current less than 4mA)
6010
h
Watchdog
8000
h
Communication error
Содержание Kuhnke FIO AI4
Страница 1: ...Instruction Manual Kuhnke FIO analogue IO Modules IP20 EtherCAT I O Modules E 747GB V2 28 01 2020...
Страница 36: ...AO4 U I 12 Bit Kendrion Kuhnke Automation GmbH 36 E 747GB V2 28 January 2020...
Страница 71: ...Kendrion Kuhnke Automation GmbH AI4 12Bit AO4 16Bit E 747GB V2 71 28 January 2020...
Страница 103: ...Kendrion Kuhnke Automation GmbH AI4 12Bit AO4 16Bit E 747GB V2 103 28 January 2020...