background image

 

Except for low output battery-operated energizers, the energizer ground rods shall penetrate the ground 
to a depth of at least 5 ft. 
Care shall be taken to avoid any damage to cables or pipelines. 
 
All energizers that are run inside buildings shall be effectively insulated from the grounded structural 
parts of the building. This may be achieved by using insulated high voltage cable. 

 

Energized leads that are run underground shall be run in a conduit of insulating material or else 
insulated high voltage cable shall be used. Care shall be taken to avoid damage to the connecting leads 
due to the effects of animal hooves or tractor wheels sinking into the ground. 

 

Any leads connected to the fence or ground shall not be installed in the same conduit as the mains 
supply wiring, communication cables or data cables. 

 

Connecting leads and electric fence wires shall not cross above overhead power or communication 
lines. 

 

Crossings with overhead power lines shall be avoided wherever possible. If such a crossing cannot be 
avoided, it shall be made underneath the power line and as nearly as possible at right angles to it. 

 

If connecting leads and electric fence wires are installed near an overhead power line, the clearances 
shall be not less than those shown in the table shown below. 

 

Power Line Voltage 

Air Distance 

 1,000 volts 

10 ft. 

> 1,000   33,000 volts 

13 ft. 

> 33,000 volts 

26 ft. 

 

If connecting leads and electric fence wires are installed near an overhead power line, their height above 
the ground shall not exceed 6.5 ft. 

 

This height applies to either side of the orthogonal projection of the outermost conductors of the power 
line on the ground surface, for a distance of 
– 6.5 ft .for power lines operating at a nominal voltage not exceeding 1,000 V; 
– 50 ft. for power lines operating at a nominal voltage exceeding 1,000 V. 

 

If connecting leads and electric fence wires are installed near a telecommunication line or a 
telecommunication cable, their distance to the line or the cable shall be at least 50 ft. 

 

Electric fences intended for deterring birds, household pet containment or training animals such as cows 
need only be supplied from low output energizers to obtain satisfactory and safe performance. 

 

In electric fences intended for deterring birds from roosting on buildings, no electric fence wire shall be 
connected to the energizer earth electrode. The earth connection has to be done with a wire on 
insulators. A warning plate, as described above, shall be fitted to every point where persons may gain 
access to the conductors. 

 
 

Where an electric animal fence crosses a public pathway, a non-electrified gate shall be incorporated in 
the electric fence at that point or a crossing by means of stiles shall be provided. At any such crossing, 
the adjacent electrified wires shall carry warning signs as described above. 

 

Electric fence energizers have to be used in accordance with the position described in the instruction 
manual. 

 

If the installation of the energizer will be inside a building, care must be taken that the electric fence 
energizer must not at all be installed in an inflammable room (stall, stable, barn). Also no easily 
inflammable materials may be stored neither close to the fence, nor close to the connections of the 
electric fence energizer. 
In an attempt to limit lightning/surge damage a lightning diverter or arrestor must be installed on the 
fence line at a point no less than 50ft. away from the energizer and its grounding system.  This diverter 
or arrestor needs to be at a point on the fence where any lightning/surge has to pass through it before 
reaching the building and fence energizer.  This must be done prior to attaching the leads on to the 
fence energizer. 
 

 

Do not connect to existing ground wires of the power supply system. 

Содержание AG M4

Страница 1: ...hecked by a technician c Functional description of the energizer with CONNECTED fence system Display OK CHECK IDEAL Output voltage 3 5 kV e g 4kV 4000V indicator light flashes green 3 5 kV indicator l...

Страница 2: ...le System 18 Lightning Protection Safety Instructions Please follow this instruction closely and store it well when not in use Electric Fences shall be installed and operated in a way that they do not...

Страница 3: ...ting at a nominal voltage exceeding 1 000 V If connecting leads and electric fence wires are installed near a telecommunication line or a telecommunication cable their distance to the line or the cabl...

Страница 4: ...rounding The correct earthing or grounding is extremely important as the complete function of the energizer depends on it After the complete installation drive in a rust protected grounding rod into t...

Страница 5: ...a voltage of 11 9V and should be reloaded without any delay In order to guarantee an optimum lifetime we advise a recharge of the battery already at a voltage of 12 1 volt Even with an only short term...

Страница 6: ...or have been installed ii products which have not been regularly and properly serviced in accordance with the Instruction Manual or Specific Operating Instructions or which have otherwise been neglect...

Страница 7: ...offer this product and the Buyer and user accept it subject to the foregoing conditions of sale and warranty which may be varied only by written agreement signed by an officer of the Manufacturer Dis...

Отзывы: