Control characteristic for factory pre-setting of 58 °C
Between 53 °C and set-point
58 °C, the throttling posi-
tions are set as a function of
temperature.
Maximum throttling position
between set-point 58 °C and 63
°C with min. volume flow.
Valve opens at > 63 °C up to
a constant throttling position
at disinfection temperature
of 70 °C.
Control characteristic