  Installation instructions  9

Spanner

Torque

wrench

Piping

Taper nut

Indoor unit piping

Model 

Suction 

(mm)

Discharge 

(mm)

Maximum 

length

Maximum 

height

KSV26CRC

6.4 (1/4")

9.5 (3/8")

15

10

KSV26HRC

6.4 (1/4")

9.5 (3/8")

15

10

KSV35CRC

6.4 (1/4")

9.5 (3/8")

20

10

KSV35HRC

6.4 (1/4")

9.5 (3/8")

20

10

KSV53HRC

6.4 (1/4")

16.0 (5/8")

25

10

KSV62HRC

6.4 (1/4")

16.0 (5/8")

20

10

KSV70CRC

6.4 (1/4")

16.0 (5/8")

25

10

KSV70HRC

6.4 (1/4")

16.0 (5/8")

25

10

KSV80HRC

6.4 (1/4")

16.0 (5/8")

25

10

Note: 
Connect the connection pipe to indoor unit at first and then 
to outdoor unit. Handle piping bending with care. Do not 
damage the connection pipe. Ensure that the joint nut is 
tightened firmly, otherwise, it may cause leakage.

Installation of outdoor unit

Electric wiring

1   Remove the handle on the right side plate of 

outdoor unit.

2   Take off wire cord anchorage. Connect and fix power 

connection cord to the terminal board. Wiring should fit 
that of indoor unit.

3   Fix the power connection cord with wire clamps and then 

connect the corresponding connector.

4   Confirm if the wire has been fixed properly.
5  Reinstall the handle.

For 2.6kW and 3.5kW units:

Handle

yellow-

brown

black

blue

2

N(1)

3

indoor unit connection

green

For 5.3kW, 6.2kW, 7.0kW and 8kW units:

Handle

yellow-

brown

black

blue

2

N(1)

3

indoor unit connection

green

Air purging and leakage test

1   Connect charging hose of manifold valve to charge end 

of low pressure valve (both high/low pressure valves 
must be tightly shut).

2  Connect joint of charging hose to vacuum pump.
3  Fully open the handle of Lo manifold valve.
4   Open the vacuum pump for vacuumisation. At the 

beginning, slightly loosen joint nut of low pressure valve 
to check if there is air coming inside. (If noise of vacuum 
pump has been changed, the reading of multimeter is 0) 
Then tighten the nut.

5   Keep vacuuming for more than 15mins and make sure the 

reading of multi-meter is -1.0 10

5

pa (-76cmHg).

6  Fully open high/low pressure valves.
7   Remove charging hose from charging end of low 

pressure valve.

8  Tighten lid of low pressure valve. (As shown in below)

Multimeter

-76cmHg

Lo handle

Charging hose

Hi handle

Charging hose

Low pressure valve

Manifold

valve

Vacuum pump

Outdoor condensate drainage (only for heat pump unit)

During heating operation, the condensate and defrosting 
water should be drained out reliably through the drain hose.
Install the outdoor drain connector in a  25mm hole on the 
base plate and attach the drain hose to the connector so 
that the waste water formed in the outdoor unit can be 
drained out. The hole diameter 25mm must be plugged.
Whether to plug other holes will be determined by the 
installer according to actual conditions.

Drain-water hole

Bottom frame

Drain plug

Hose (available commercially,

inner diameter 16mm)

Drain connecter

Содержание KSV80HRC

Страница 1: ...Inverter Split Room Air Conditioner Installation Manual KSV26CRC KSV26HRC KSV35CRC KSV35HRC KSV53HRC KSV62HRC KSV70CRC KSV70HRC KSV80HRC Refrigerant R410A...

Страница 2: ...to discard this air conditioner please contact your local authorities and ask for the correct method of disposal caution The air conditioner is not intended for use by young children or infirmed perso...

Страница 3: ...uits must be disconnected Please read this installation manual and the user manual before installation and store in a handy place for later reference Inside you will find many helpful hints on how to...

Страница 4: ...tic waves are generated by radio equipment welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains...

Страница 5: ...sions are not adhered to the air conditioner will not perform to specification may not be able to be serviced and the warranty may be voided The installation must allow for reasonable access space nec...

Страница 6: ...tside the outlet pipe The drain hose should be slanted downward slightly without distortion bulge or fluctuation Do not put the outlet into water Installation of indoor unit Installation of the mounti...

Страница 7: ...om the left or right side of indoor unit cut off the tailings from the chassis when necessary As shown in Fig 1 a Cut off the tailings 1 when routing the wiring only b Cut off the tailings 1 and taili...

Страница 8: ...nt leakage is due to defects in the flaring work Carry out correct flaring work using the following procedure Oblique 90 C Roughness Burr A Cut the pipes and the cable Use the piping kit accessory if...

Страница 9: ...connection green Air purging and leakage test 1 Connect charging hose of manifold valve to charge end of low pressure valve both high low pressure valves must be tightly shut 2 Connect joint of chargi...

Страница 10: ...city is not accurate Operation test 1 Before operation test a Do not switch on power before installation is finished completely b Electric wiring must be connected correctly and securely c Cut off val...

Страница 11: ...less the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii mis...

Страница 12: ...bout Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www ke...

Отзывы: