8  Installation instructions  

Kelvinator Air Conditioning

Outer diameter (mm)

A(mm)

Max.

Min.

φ

6.35

1.3

0.7

φ

9.53

1.6

1.0

φ

12.7

1.8

1.0

φ

16.0

2.4

2.2

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A

"

Tightening connection

•  Align the centre  of the pipes.
•   Sufficiently tighten the flare nut with fingers, and 

then tighten it with a spanner and torque wrench 
as shown below.

Indoor unit tubing

Flare nut

Piping

s

Outer 

diameter

Tightening torque 

(Kg.m)

Additional tightening 

torque (Kg.m)

φ

6.35

1.6

2.0

φ

9.53

3.0

3.5

φ

12.7

5.0

5.5

φ

16.0

7.5

8.0

caution

•   Excessive torque can break nut depending on 

installation conditions.

E:  Check

•  Compare the flared work with the adjacent diagram.
•   If flare is found to be defective, cut off the flared section 

and do flaring work again.

Smooth all round

 Improper flaring

Even length

all round

Flaring work

Main cause for refrigerant leakage is due to defects in 
the flaring work. Carry out correct flaring work using the 
following procedure:

Oblique

90 C

Roughness

Burr

A:  Cut the pipes and the cable

•   Use the piping kit accessory (if applicable) or pipes 

purchased locally.

•   Measure the distance between the indoor and the 

outdoor unit.

•  Cut the pipes a little longer than the measured distance.
•  Cut the cable 1.5m longer than the pipe length.

B:  Burr removal

•   Completely remove all burrs from the cut cross section 

of pipe/tube.

•   Face the end of the copper pipe/tube in a downward 

direction as you remove burrs in order to avoid burrs 
dropping into the tubing.

Pipe

Reamer

Face down

caution

C:  Putting flare nut on

•  Remove flare nuts attached to indoor and outdoor unit, 
 

then put them on pipe/tube having completed burr  

 removal.

Note: It is not possible to put them on after flaring work.

Flare nut

Copper tube

D:  Flaring work

•  Carry out flaring work using flaring tool as shown below.
•   Firmly hold copper pipe in a die according to the 

dimension shown in the following table.

Refrigerant pipe connection

Содержание KSV26CRC

Страница 1: ...Inverter Split Room Air Conditioner Installation Manual KSV26CRC KSV26HRC KSV35CRC KSV35HRC KSV53HRC KSV62HRC KSV70CRC KSV70HRC KSV80HRC Refrigerant R410A ...

Страница 2: ... to discard this air conditioner please contact your local authorities and ask for the correct method of disposal caution The air conditioner is not intended for use by young children or infirmed persons without supervision Young children should be supervised to ensure that they do not play with the air conditioner Contact an authorised installer for installation of this unit Contact an authorised...

Страница 3: ...cuits must be disconnected Please read this installation manual and the user manual before installation and store in a handy place for later reference Inside you will find many helpful hints on how to install and test the air conditioner properly Electrical work must be carried out by a licensed electrician Be sure to use the correct rating of the power plug and main circuit for the model to be in...

Страница 4: ...etic waves are generated by radio equipment welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot spring zones corrosion or poor air quality exists Installation site of indoor unit 1 The air inlet and outlet should be away from the obstructions Ensure the air can be...

Страница 5: ...nsions are not adhered to the air conditioner will not perform to specification may not be able to be serviced and the warranty may be voided The installation must allow for reasonable access space necessary for proper installation of the unit include the minimum permissible distances to adjacent parts Space to the wall 200cm above 30cm above Space to the obstruction Air outlet side e v o b 50cm a...

Страница 6: ...outside the outlet pipe The drain hose should be slanted downward slightly without distortion bulge or fluctuation Do not put the outlet into water Installation of indoor unit Installation of the mounting plate 1 The mounting plate must be installed horizontally As the water tray s outlet for the indoor unit is two way during installation the indoor unit should slightly slant to water tray s outle...

Страница 7: ...rom the left or right side of indoor unit cut off the tailings from the chassis when necessary As shown in Fig 1 a Cut off the tailings 1 when routing the wiring only b Cut off the tailings 1 and tailings 2 when routing both the wiring and piping 2 Take out the piping from body case wrap the piping power cords drain hose with the tape and then make them pass through the piping hole As shown in Fig...

Страница 8: ...igerant leakage is due to defects in the flaring work Carry out correct flaring work using the following procedure Oblique 90 C Roughness Burr A Cut the pipes and the cable Use the piping kit accessory if applicable or pipes purchased locally Measure the distance between the indoor and the outdoor unit Cut the pipes a little longer than the measured distance Cut the cable 1 5m longer than the pipe...

Страница 9: ... connection green Air purging and leakage test 1 Connect charging hose of manifold valve to charge end of low pressure valve both high low pressure valves must be tightly shut 2 Connect joint of charging hose to vacuum pump 3 Fully open the handle of Lo manifold valve 4 Open the vacuum pump for vacuumisation At the beginning slightly loosen joint nut of low pressure valve to check if there is air ...

Страница 10: ...acity is not accurate Operation test 1 Before operation test a Do not switch on power before installation is finished completely b Electric wiring must be connected correctly and securely c Cut off valves of the connection pipes should be opened d All the impurities such as scraps and waste must be cleared from the unit 2 Operation test method a Switch on power and press ON OFF button on the remot...

Страница 11: ...nless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage or incorrect power supply v incomplete or improper installation vi inco...

Страница 12: ...about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www kelvinator com au Kelvinator We are part of the Electrolux family Share more of our thinking at www electrolux com au ...

Отзывы: