background image

FOOD PREP TABLES

CONTROL PANEL SOLID-STATE THERMOSTAT 

FRONT PANEL COMMANDS
SET

 

SET: To display target set point; in programming mode, it selects a 
parameter or confirms an operation.

 

DEF: To start a manual defrost

 

UP: To view last alarm occurrence; in programming mode, it browses the 
parameter codes or increases the display value

 

DOWN: To view last alarm occurrence; in programming mode, it browses 
the parameter codes or decreases the display value

Key Combination:

  To lock & unlock the keyboard

  To enter in programming mode
  To return to the room temperature display

LED

MODE

FUNCTION

On

Compressor enabled

Flashing Programming phase (flashing with  )

Anti-short cycle delay enabled

On

Defrost enabled

Flashing Programming phase (flashing with  )

Dripping in progress

On

Fans enabled

Flashing Fans delay after defrost in progress

On

A temperature alarm happened

MAIN FUNCTIONS
1.  How to See the Setpoint

1.  Push and immediately release the 

SET

 key: the display will show the set 

point value.

2.  Push and immediately release the 

SET

 key or wait for 5 seconds to display 

the sensor value again.

2.  How to Change the Setpoint

1. Hold 

the 

SET

 key for more than 2 seconds to change the set point value.

2.  The value of the set point will be displayed and the 

 LED starts blinking.

3.  To change the set value, push the   or   key within 10 seconds.
4.  To set new point value, push the 

SET

 key again or wait 10 seconds.

3.  How to Start a Manual Defrost

1.  Hold the 

 key for more than 2 seconds and a manual defrost will start.

4.  How to Lock the Keyboard

1.  Hold the   and   keys for more than 3 seconds.
2.  The “POF” message will be displayed and the keyboard will be locked. At 

this point, it will be possible only to see the set point or the MAX or MIN 
temperature stored.

3.  If a key is pressed for more than 3 seconds, the ”POF” message will be 

displayed.

5.  How to Unlock the Keyboard

1.  Hold the   and   keys together for more than 3 seconds, until the “POF” 

message is displayed.

ALARM SIGNALS
How to See the Alarm and Reset the Recorded Alarm

1.  Hold the   or   key to display the alarm signals.
2.  When the signal is displayed, hold the 

SET

 key until the “rst” message is 

displayed. Push the 

SET

 key again. The “rst” message starts blinking and the 

normal temperature will be displayed again.

MESSAGE

CAUSE

OUTPUTS

“P1”

Room probe failure

Compressor output according 

to par. “Con” and “COF”

“P2”

Evaporator probe failure

Defrost end is timed

“HA”

Maximum temperature alarm

Outputs unchanged

“LA”

Minimum temperature alarm

Outputs unchanged

“dA”

Door open

Compressor and fans restarts

“EA”

External alarm

Output unchanged

“CA”

Serious external alarm (i1F=bAL)

All outputs OFF

“CA”

Pressure switch alarm (i1F=PAL)

All outputs OFF

MAINTENANCE

DANGER:  THE POWER SWITCH MUST BE TURNED OFF AND THE UNIT DISCONNECTED 

FROM THE POWER SOURCE WHENEVER PERFORMING SERVICE, 

MAINTENANCE FUNCTIONS OR CLEANING THE REFRIGERATED AREA.

DANGER:  NEVER USE A HIGH PRESSURE WATER WASH FOR THIS CLEANING 

PROCEDURE AS WATER CAN DAMAGE THE ELECTRICAL COMPONENTS 

LOCATED NEAR OR AT THE CONDENSER COIL. 

DANGER:  NEVER USE STEEL PADS, WIRE BRUSHES OR SCRAPERS!
CAUTION:  NEVER USE AN ACID BASED CLEANING SOLUTION!MANY FOOD PRODUCTS 

HAVE AN ACIDIC CONTENT WHICH CAN DETERIORATE THE FINISH. BE SURE 

TO CLEAN THE STAINLESS STEEL SURFACES OF ALL FOOD PRODUCTS.

REFRIGERATORS AND FREEZERS

The interior and exterior can be cleaned using soap and warm water. If this isn’t 
sufficient, try ammonia and water or a nonabrasive liquid cleaner. When cleaning 
the exterior, always rub with the “grain” of the stainless steel to avoid marring 
the finish.
Do not use an abrasive cleaner because it will scratch the stainless steel and 
plastic and can damage the breaker strips and gaskets.

CLEANING THE CONDENSER COIL

The condenser coil requires regular cleaning. Cleaning is recommended every 
90 days. In some instances, you may find that there is a large amount of debris 
and dust or grease accumulated prior to the 90 day time frame. In these cases 
the condenser coil should be cleaned every 30 days.
If the build up on the coil consists of only light dust and debris, the condenser 
coil can be cleaned with a simple brush. Heavier dust build-up may require a 
vacuum or even compressed air to blow through the condenser coil.

Содержание KCHST27.8

Страница 1: ...efrigerators and freezers is located inside the unit on the left hand side near the top on the wall Always have the serial number of your unit available when calling for parts or service This manual covers standard units only If you have a custom unit consult the customer service department at the number listed in this manual USA Canada 866 738 1640 4003 Collins Lane Louisville KY 40245 www kelvin...

Страница 2: ...EARS NOTE DO NOT STORE EXPLOSIVE SUBSTANCES SUCH AS AEROSOL CANS WITH A FLAMMABLE PROPELLANT IN THIS APPLIANCE NOTE THE APPLIANCE USE FLAMMABLE INSULATION BLOWING GAS C5H10 DISPOSAL OF THE APPLIANCE SHALL IN ACCORDANCE WITH THE REGULATIONS OF LOCAL AUTHORITIES NOTE THE KEY FOR APPLIANCE ELECTRIC BOX SHOULD BE SAFE KEPT BY QUALIFIED PERSONS IN ORDER TO AVOID A HAZARD WARNING KEEP VENTILATION OPENIN...

Страница 3: ...e air Avoid hot corners and locations near stoves and ovens It is recommended that the unit be installed no closer than 2 from any wall LEVELING A level cabinet looks better and will perform better because the doors will line up with the frames properly Use a level to make sure the unit is level from front to back and side to side Units supplied with legs will have adjustable bullet feet to make t...

Страница 4: ... 1 Hold the or key to display the alarm signals 2 When the signal is displayed hold the SET key until the rst message is displayed Push the SET key again The rst message starts blinking and the normal temperature will be displayed again MESSAGE CAUSE OUTPUTS P1 Room probe failure Compressor output according to par Con and COF P2 Evaporator probe failure Defrost end is timed HA Maximum temperature ...

Страница 5: ...ease should be cleaned with a non abrasive cleaner and plastic scrub pad It is always good to rub with the grain of the steel There are also stainless steel cleaners available which can restore and preserve the finish of the steels protective layer Early signs of stainless steel breakdown can consist of small pits and cracks If this has begun clean thoroughly and start to apply stainless steel cle...

Страница 6: ...8R KCHUCWT48R KCHUC60R KCHUCWT60R CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 PLUG THERMOSTAT DISPLAY ROOM EVAP SENSOR CONDENSEN FAN OVERLOAD PROTECTOR COMPRESSOR FAN POWER EVAP FAN DOOR SWITCH PTC STARTER PLUG THERMOSTAT DISPLAY ROOM EVAP SENSOR CONDENSEN FAN OVERLOAD PROTECTOR COMPRESSOR FAN POWER EVAP FAN DOOR SWITCH PTC STARTER ...

Страница 7: ...FOR REPLACEMENT PARTS 866 738 1640 PLUG THERMOSTAT DISPLAY ROOM EVAP SENSO R CONDENSEN FAN OVERLOAD PROTECTOR COMPRESSOR CURRENT RELAY STARTING CAPACITOR FAN POWER EVAP FAN DOOR SWITCH L N PLU G THERMOSTAT DISPLA Y CONDENSER FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR PTC STARTER CIRCUITALION FAN MOTOR t C L N ROOM EVAP SENSOR DOOR FRAME HEATER ...

Страница 8: ...ALION FAN MOTOR ROOM EVAP SENSOR DOOR FRAME HEATER MIDDLE FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR STARTING CAPACITOR OVERLOAD PROTECTOR COMPRESSOR CURRENT RELAY THERMOSTAT DISPLAY M M L N THERMOSTAT DISPLAY PLUG CIRCUITALION FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR ROOM EVAP SENSO R DOOR FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR STARTIN G CAPACITO R CURRENT RELAY ...

Страница 9: ...T60 24 KCHMT60 24 2D CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 PLUG CIRCUITALION FAN MOTOR ROOM EVAP SENSOR THERMOSTAT DISPLAY DOOR FRAME HEATER CONDENSER FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR PTC STARTER L N PLUG CIRCUITALION FAN MOTOR L N ROOM EVAP SENSOR THERMOSTAT DISPLAY DOOR FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR PTC STARTER ...

Страница 10: ...738 1640 PLUG CIRCUITALION FAN MOTOR THERMOSTAT DISPLAY ROOM EVAP SENSOR DOOR FRAME HEATER MIDDLE FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR PTC STARTER L N PLUG THERMOSTAT DISPLAY ROOM EVAP SENSO R FAN THERMAL CUT OFF DEFROST HEATER OVERLOAD PROTECTOR COMPRESSOR CURRENT RELAY STARTING CAPACITOR FAN POWER EVAP FAN DOOR SWITCH N L CONDENSER ...

Страница 11: ...8F CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 PLUG THERMOSTAT DISPLAY ROOM EVAP SENSOR FAN THERMAL CUT OFF DEFROST HEATER OVERLOAD PROTECTOR COMPRESSOR CURRENT RELAY STARTING CAPACITOR MIDDLE FRAME HEATER FAN POWER EVAP FAN DOOR SWITCH N L CONDENSER ...

Страница 12: ...12 FOOD PREP TABLES Wiring Diagram KCHUC27R KCHUCWT27R KCHUC27 2DR CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 13: ...13 FOOD PREP TABLES Wiring Diagram KCHUC48R KCHUCWT48R KCHUC60R KCHUCWT60R CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 14: ...14 FOOD PREP TABLES Wiring Diagram KCHUC72R KCHUCWT72R CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 15: ...15 FOOD PREP TABLES Wiring Diagram KCHST27 8 KCHMT29 12 KCHMT29 12 2D CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 16: ...16 FOOD PREP TABLES Wiring Diagram KCHST48 12 KCHMT48 18 KCHMT48 18 2D KCHST60 16 KCHMT60 24 KCHMT60 24 2D CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 17: ...17 FOOD PREP TABLES Wiring Diagram KCHST70 18 KCHMT70 30 CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 18: ...18 FOOD PREP TABLES Wiring Diagram KCHPT50 6 CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 19: ...19 FOOD PREP TABLES Wiring Diagram KCHPT60 9 CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 20: ...20 FOOD PREP TABLES Wiring Diagram KCHPT70 12 CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 21: ...21 FOOD PREP TABLES Wiring Diagram KCHUC27F KCHUCWT27F CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 22: ...22 FOOD PREP TABLES Wiring Diagram KCHUC48F KCHUCWT48F CALL FACTORY FOR REPLACEMENT PARTS 866 738 1640 ...

Страница 23: ...lls etc 14 Damages caused by services performed by unauthorized service companies use of parts other than genuine Electrolux parts or parts obtained from persons other than authorized service companies or external causes such as abuse misuse inadequate power supply accidents fires or acts of God 15 For appliances operated by a concessionaire or vendor in a trailer or other motorized vehicle or at ...

Страница 24: ...24 FOOD PREP TABLES Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By ...

Страница 25: ...NVÍO LB KG ENCHUFE NEMA ALMACENAMIENTO PIES3 M3 ESTANTE PIES2 M2 KCHST27 8 115 60 1 3 0 7 0 20 14 1 3 8 1 3 853 3 0 276 125 5 15P KCHST48 12 115 60 1 4 3 12 0 34 26 2 41 12 1 2 1365 3 17 313 142 5 15P KCHST60 16 115 60 1 4 3 15 5 0 44 30 2 79 16 1 2 1365 3 17 362 164 5 15P KCHST70 18 115 60 1 4 3 18 0 51 36 3 34 18 1 2 1365 3 17 408 185 5 15P UNIDADES MEGATOP PARA SÁNDWICHES ENSALADAS N º DE MODEL...

Страница 26: ...UTILIZA GAS INFLAMABLE DE AISLAMIENTO C5H10 LA ELIMINACIÓN DEL EQUIPO DEBE HACERSE DE ACUERDO CON LAS NORMAS DE LAS AUTORIDADES LOCALES NOTA LA LLAVE DE LA CAJA ELÉCTRICA DEL EQUIPO DEBE GUARDARLA PERSONAL PROFESIONAL PARA EVITAR RIESGOS ADVERTENCIA MANTENGA LIBRES DE OBSTRUCCIONES LAS ABERTURAS DE VENTILACIÓN DEL ALOJAMIENTO DEL EQUIPO O DE LA ESTRUCTURA EMPOTRADA ADVERTENCIA NO UTILICE DISPOSITI...

Страница 27: ...s Se recomienda que la unidad no se instale a menos de 2 5 cm de cualquier pared NIVELACIÓN Un armario nivelado se ve bien y funciona mejor debido a que las puertas se alinearán correctamente con los marcos Utilice un nivel para comprobar que la unidad esté nivelada de delante a atrás y de lado a lado Las unidades suministradas con patas tienen patas regulables para que se realicen los ajustes nec...

Страница 28: ...ce el mensaje POF y se bloquea el teclado En ese momento solo es posible ver el ajuste de referencia o la temperatura MAX o MIN almacenada 3 Si se presiona una tecla durante más de 3 segundos se muestra el mensaje POF 5 Cómo desbloquear el teclado 1 Mantenga presionadas las teclas y durante más de 3 segundos hasta que aparezca el mensaje POF SEÑALES DE ALARMA Cómo ver la alarma y restablecer la al...

Страница 29: ...ina o no contener base de cloruro Cualquier limpiador que contenga cloruros dañará la película protectora del acero inoxidable Los cloruros también suelen encontrarse en el agua dura sales y limpiadores domésticos e industriales Si utiliza limpiadores que contengan cloruros asegúrese de enjuagar y de secar por completo La limpieza habitual del acero inoxidable puede efectuarse con jabón y agua Las...

Страница 30: ...bleado KCHUC48R KCHUCWT48R KCHUC60R KCHUCWT60R LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 PLUG THERMOSTAT DISPLAY ROOM EVAP SENSOR CONDENSEN FAN OVERLOAD PROTECTOR COMPRESSOR FAN POWER EVAP FAN DOOR SWITCH PTC STARTER PLUG THERMOSTAT DISPLAY ROOM EVAP SENSOR CONDENSEN FAN OVERLOAD PROTECTOR COMPRESSOR FAN POWER EVAP FAN DOOR SWITCH PTC STARTER ...

Страница 31: ...E A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 PLUG THERMOSTAT DISPLAY ROOM EVAP SENSOR CONDENSEN FAN OVERLOAD PROTECTO R COMPRESSO R CURREN T RELAY STARTING CAPACITO R FAN POWE R EVAP FAN DOOR SWITCH L N PLUG THERMOSTAT DISPLAY CONDENSE R FAN MOTO R OVERLOAD PROTECTO R COMPRESSOR PTC STARTER CIRCUITALION FAN MOTO R t C L N ROOM EVAP SENSO R DOOR FRAME HEATER ...

Страница 32: ...M M L N PLUG CIRCUITALION FAN MOTOR ROOM EVAP SENSOR DOOR FRAME HEATER MIDDLE FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR STARTING CAPACITOR OVERLOAD PROTECTOR COMPRESSOR CURRENT RELAY THERMOSTAT DISPLAY M M L N THERMOSTAT DISPLAY PLUG CIRCUITALION FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR ROOM EVAP SENSOR DOOR FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR STARTING CAPACITOR CURREN T...

Страница 33: ...HST60 16 KCHMT60 24 KCHMT60 24 2D LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 PLUG CIRCUITALION FAN MOTOR ROOM EVA P SENSOR THERMOSTAT DISPLAY DOOR FRAME HEATER CONDENSER FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR PTC STARTER L N PLUG CIRCUITALION FAN MOTOR L N ROOM EVAP SENSOR THERMOSTAT DISPLAY DOOR FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR PTC STA...

Страница 34: ...A REPUESTOS 866 738 1640 PLUG CIRCUITALIO N FAN MOTOR THERMOSTAT DISPLAY ROOM EVAP SENSOR DOOR FRAME HEATER MIDDLE FRAME HEATER MIDDLE FRAME HEATER CONDENSER FAN MOTOR OVERLOAD PROTECTOR COMPRESSOR PTC STARTER L N PLU G THERMOSTAT DISPLAY ROOM EVAP SENSOR FAN THERMA L CUT OFF DEFROST HEATER OVERLOAD PROTECTO R COMPRESSO R CURRENT RELAY STARTING CAPACITOR FAN POWE R EVAP FAN DOOR SWITCH N L CONDENS...

Страница 35: ...CHUCWT48F LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 PLUG THERMOSTAT DISPLAY ROOM EVAP SENSOR FAN THERMAL CUT OFF DEFROST HEATER OVERLOAD PROTECTOR COMPRESSOR CURRENT RELAY STARTING CAPACITOR MIDDLE FRAME HEATER FAN POWER EVAP FAN DOOR SWITCH N L CONDENSER ...

Страница 36: ...12 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHUC27R KCHUCWT27R KCHUC27 2DR LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 37: ...13 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHUC48R KCHUCWT48R KCHUC60R KCHUCWT60R LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 38: ...14 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHUC72R KCHUCWT72R LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 39: ...15 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHST27 8 KCHMT29 12 KCHMT29 12 2D LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 40: ...16 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHST48 12 KCHMT48 18 KCHMT48 18 2D KCHST60 16 KCHMT60 24 KCHMT60 24 2D LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 41: ...17 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHST70 18 KCHMT70 30 LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 42: ...18 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHPT50 6 LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 43: ...19 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHPT60 9 LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 44: ...20 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHPT70 12 LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 45: ...21 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHUC27F KCHUCWT27F LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 46: ...22 MESAS DE PREPARACIÓN ALIMENTOS Diagrama de cableado KCHUC48F KCHUCWT48F LLAME A LA FÁBRICA SI NECESITA REPUESTOS 866 738 1640 ...

Страница 47: ...les de Electrolux Professional o repuestos obtenidos de personas que no sean empresas de servicios autorizadas o causas externas como uso incorrecto o indebido alimentación eléctrica inadecuada accidentes incendios o desastres naturales 15 Los equipos utilizados por concesionarios o distribuidores en un remolque u otro vehículo motorizado o en distintas ubicaciones tienen garantía de un 1 año con ...

Страница 48: ...CIÓN ALIMENTOS Registro de servicio N º de modelo Adquirido a Nº de serie Ubicación Fecha de compra Fecha de instalación N º de orden de compra Para llamadas al servicio técnico Fecha Mantenimiento realizado Realizado por ...

Отзывы: