Installation 

SNA-Series Tankless Heater

Keltech • 

215-1815 Rev. B; ECN 130011 

10/17/2014

Non Type Z Pressurized Equipment

An alarm shall be provided to indicate failure of the protective gas supply to maintain the required pressure . Piping for 
the protective gas shall be protected against mechanical damage .
Where the compressor intake line passes through a classified location, it shall be constructed of noncombustible 
material, designed to prevent leakage of flammable gases, vapors, or dusts into the protective gas, and protected 
against mechanical damage and corrosion .
The electrical power for the protective gas supply (blower, compressor, etc .) shall be supplied either from a separate 
power source or from the protected enclosure power supply prior to any service disconnects of the protected 
enclosure . Any protected enclosure that can be isolated from the protective gas supply shall be equipped with an 
alarm . Where an alarm is used to indicate the loss of pressure in the cabinet:

•  The alarm shall be located at a constantly attended location .
•  The alarm actuator shall take its signal from the protected enclosure and shall not be installed between the 

enclosure and the protective gas supply .

•  The alarm actuator shall be mechanical, pneumatic, or electrical .
•  Electrical alarms and electrical alarm actuators shall be approved for the location in which they are installed .
•  No valves shall be permitted between the alarm actuator and the enclosure .

Intrinsically Safe (IS) Installation

FIGURE 7

1 .  Electrical equipment connected to associated apparatus should not use or generate more than 250 volts .
2 .  Installation shall be in accordance with the manufacturer's instructions and the National Electrical Code  

(ANSI/NFPA 70)

3 .  For guidance on Installation see ANSI/ISA RP12 .6 (Installation of IS Instrument System in Class I 

Hazardous Locations) .

4 .  Voc or Vt of associated apparatus is less than Vmax 

Isc or IT of associated apparatus is less than Imax 
Ci plus capacitance of interconnecting cabling is less than Ca of the associated apparatus 
Li plus inductance of interconnecting cabling is less than La fo the associated apparatus

5 .  "Simple Apparatus" is a device that will not generate or store more than 1 .2V, 0,1A, 25mW or 20uJ 

Hazardous Location 
Class I , Division 2 
Groups A, B, C, D 
T5 Hazardous (classified) Areas

MiniPurge: Option Code /IS 
Vmax = 30v 
Imax = 350mA 
Ci = 0 Li = 0

Non- Hazardous Location 
(or suitably protected enclosure)

Power Supply

Outputs to relays or 
power contactors

Intrinsically Safe 
Interface Unit

Simple apparatus 
device

Содержание SNA-36

Страница 1: ...ptions 11 12 Maintenance 12 Troubleshooting 12 13 Special Installation Operating Instructions 14 17 IMPORTANT Read this entire installation manual to ensure proper installation When finished with the...

Страница 2: ...ntended service Frequency of cleaning and inspection depends upon local water conditions For heaters with adjustable output temperatures check and adjust as needed at initial installation and on a qua...

Страница 3: ...eaters from Rain or other falling precipitation via tarp or other waterproof media Runoff and accumulation of groundwater from any source that may exceed 1 inch NOTE For heaters with ENHT freeze prote...

Страница 4: ...mperature relief valve on hot water outlet immediately following the union NOTE Valve must empty into a drain See Figure 2 B Remove air by re installing drain plugs and open inlet supply valve to appl...

Страница 5: ...stem or at any drop to eliminate trapped air Components Needed 5 Union 1 1 4 Shutoff Valve Pressure and Temperature Relief Valve 150 psi Y Strainer 100 mesh or Inline Filter 150 microns 2 Gate or Ball...

Страница 6: ...rating for each heater CAUTION To avoid damage to the electronics or internal wiring do not perform any brazing or sweat soldering inside the enclosure ELECTRICAL SPECIFICATIONS FOR HEATER PHASE 3 Mo...

Страница 7: ...ief valve on outlet if required by local or national plumbing codes If the hot water process is not at the highest point in the plumbing loop then an automatic air vent valve must be added at the high...

Страница 8: ...et shower etc then flush the system for 5 minutes to ensure all air is purged from the system CAUTION Failure to bleed air properly will damage elements and cause heater malfunction Be sure that plumb...

Страница 9: ...me page Advance Key Advances through parameter prompts Auto Man Off C r71 Turns Control Loop On Manual Off Disabled on SNA Models XX X h Pr1 Heater Power Disabled on SNA Models no AUt1 Autotune Contac...

Страница 10: ...e of approximately 10 psi For example if the high limit pressure is 40 psi adjust the low limit pressure to 30 psi with the pressure switch located on the supply pump Heater will not energize heating...

Страница 11: ...fault After turning on water then power test ground fault 1 Press GF Test button 2 Watch for ground fault light to illuminate and Bank Ready light s to shut off The Ground Fault system is active and...

Страница 12: ...he heat exchangers may trip at temperatures below 32 F on heaters equipped with ENHT or ENHT30 Manual resets are set to trip at 100 F 38 C Heat trace installed on connected piping can heat water to te...

Страница 13: ...dicated Bank 1 2 on the front bezel Bank 1 on the FLCB Bank 3 4 on the front bezel Bank 2 on the FLCB If the light is off and there is power on Check if water temperature is greater than 175 F Decreas...

Страница 14: ...nlet fitting here FIGURE 6 EXP2 EXP2LC Installation Notes 1 Any tubing conduit or fittings connected to the Pressurized Enclosure PE must conform to local codes for flammability ratings 2 All egress i...

Страница 15: ...ure and the protective gas supply The alarm actuator shall be mechanical pneumatic or electrical Electrical alarms and electrical alarm actuators shall be approved for the location in which they are i...

Страница 16: ...roved the interior of the PE is gas free and checked that the Pressurized indicator is green Commissioning Test Commissioning Leakage Compensation LC and Continuous Flow High Purge Keltech Options EXP...

Страница 17: ...larms function correctly Check the Relief Valve and any other Spark Arrestors Remove any debris or corrosion or replace the Spark Arrestor Check the condition of the air supply filter element Clean or...

Отзывы: